Plan Review Notes For Permit 05090055 |
Permit Number |
05090055 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2006-04-03 00:00:00 | *** DENIED *** | | 1) ENERGY CALCULATIONS ARE CALLING FOR | | 20,400 TOTAL BTU'S, MECHANICAL PLANS ARE | | CALLING FOR 38,000 TOTAL BTU'S, THE | | PLANS CAN NOT CALL FOR MORE TOTAL BTU'S | | THAN THE ENERGY CAL'S. PLEASE CORRECT. | | | | 2) MANUAL J CALCULATIONS ARE CALLING FOR | | 15,125 SENSIBLE BTU'S AND THE MECHANICAL | | PLANS ARE CALLING FOR 29,000 SENSIBLE | | BTU'S, THE PLANS CAN ONLY CALL FOR 20% | | MORE THAN THE MANUAL J CAL'S. PER 2004 | | FBC CH. 13 607.1.ABC.1.1 PLEASE CORRECT. | | | | 3) ENERGY CALCULATIONS ARE CALLING FOR 5 | | KW HEAT AND THE MECHANICAL PLANS ARE | | CALLING FOR 10 KW HEAT, THE PLANS CAN | | NOT CALL FOR MORE THAN THE ENERGY CAL'S. | | PLEASE CORRECT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|