2006-04-03 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS ARE CALLING FOR
 20,400 TOTAL BTU'S, MECHANICAL PLANS ARE
 CALLING FOR 38,000 TOTAL BTU'S, THE
 PLANS CAN NOT CALL FOR MORE TOTAL BTU'S
 THAN THE ENERGY CAL'S. PLEASE CORRECT.
  
 2) MANUAL J CALCULATIONS ARE CALLING FOR
 15,125 SENSIBLE BTU'S AND THE MECHANICAL
 PLANS ARE CALLING FOR 29,000 SENSIBLE
 BTU'S, THE PLANS CAN ONLY CALL FOR 20%
 MORE THAN THE MANUAL J CAL'S. PER 2004
 FBC CH. 13 607.1.ABC.1.1 PLEASE CORRECT.
  
 3) ENERGY CALCULATIONS ARE CALLING FOR 5
 KW HEAT AND THE MECHANICAL PLANS ARE
 CALLING FOR 10 KW HEAT, THE PLANS CAN
 NOT CALL FOR MORE THAN THE ENERGY CAL'S.
 PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.