Plan Review Notes
Plan Review Notes For Permit 05090055
Permit Number 05090055
Review Stop G
Sequence Number 2
Notes
Date Text
2006-12-28 13:00:01CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL INSPECTION.
 THE SUBMITTED GAS RISER DIAGRAM CAN'T BE A REVISION
 BECAUSE THERE IS NO GAS PERMIT.
  
 PLEASE NOTE THAT THE SUBMITTED GAS RISER DIAGRAM IS NOT
 SIZED CORRECTLY PER THE FOLLOWING TABLES.
 A} NFPA (ONLINE) TABLE 6.2(B) SCHEDULE 40 METALLIC PIPE
 BECAUSE FBC-2004 FUEL GAS TABLE, 402.4 (2) ONLY GOES TO
 200'.
 B} NFPA (ONLINE) TABLE 6.2(S) POLYETHYLENE PLASTIC PIPE
 BECAUSE FBC-2004 FUEL GAS TABLE, 402.4 (20) ONLY GOES
 TO 200'.
 C} FBC-2004 FUEL GAS TABLE 402.4 (14) CSST.
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721