Plan Review Notes
Plan Review Notes For Permit 05090055
Permit Number 05090055
Review Stop G
Sequence Number 1
Notes
Date Text
2006-11-30 08:41:19REVISION UNSAT
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE.
  
 1. PLEASE NOTE THAT A SEPERATE GEN/RES PERMIT IS
 REQUIRED FOR THE GENERATOR AND THAT A GAS PERMIT CAN
 NOT BE ISSUED UNTIL ONE HAS BEEN APPLIED FOR AND
 ZONING, ELECTRICAL AND GAS HAS APPROVED THE GENERATOR
 LOCATION. OR YOU CAN INDICATE ON THE DRAWINGS THAT THE
 GENERATOR IS A "FUTURE" GENERATOR.
  
 ******IMPORTANT INFORMATION******
 AS OF 8/25/06 GENERATOR (GEN/RES AND
 GEN/COM) PERMIT APPLICATIONS SHALL NOT
 BE ACCEPTED UNLESS THE ELECTRICAL INFOR-
 MATION AND GAS (OR DIESEL) INFORMATION
 IS ALL SUBMITTED AT THE SAME TIME. THE
 GENERATOR, ELECTRICAL AND GAS/DIESEL IN-
 FORMATION WILL BE ROUTED TOGETHER. THIS
 WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY
 THE MANUFACTURER'S SPECI-
 FICATIONS AND INSTALLATION INSTRUCTIONS)
 ARE AVAILABLE TO ALL PLAN REVIEWERS.
  
 2. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: NOT ALL CUT SECTIONS OF PIPE HAVE CORRESPONDING
 LENGTHS INDICATED ON THE GAS RISER DIAGRAM ON SHEET
 A-3.
  
 3. PLEASE INDICATE THE TYPE OF GAS, (LP OR NATURAL) ON
 SHEET A-3 GAS RISER DIAGRAM.
  
 4.PLEASE INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI ON SHEET A-3 GAS
 RISER DIAGRAM.
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 NOTE: NEED MANUFACTURER SHEETS OF MP REGULATORS IF GAS
 SYSTEM IS 2PSI. ALSO NEED MANUFACTURER SHEETS AND
 INSTALLATION INSTRUCTIONS ON GENERATOR TO VERIFY BTU
 LOAD AND MINIMUM INSTALLATION CLEARENCES TO
 STRUCTURES.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved