Plan Review Notes For Permit 05090028 |
Permit Number |
05090028 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-09-09 00:00:00 | DENIED | | | | 1) ENGINEERING IS INCORRECT. THE MAXIMUM | | DESIGN PRESSURE FOR THE SYSTEM BEING | | USED IS BETWEEN -45 AND -75 CONTRACTOR | | MUST SPECIFY ONE FROM PAGE 21 OF THE | | PRODUCT APPROVAL THAT WAS SUBMITTED. IN | | ORDER FOR THE SYSTEM TO RESIST THE | | PERMETER AND CORNER PRESSURES ENHANCED | | FASTENING WILL BE REQUIRED. THIS MEANS | | THAT THE DISTANCE BETWEEN THE FASTENERS | | SPECIFIED IN THE PRODUCT APPROVAL MUST | | BE REDUCED. NOT INCREASED AS INDICATED | | BY ENGINEER'S REPORT. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | |
|