Plan Review Notes
Plan Review Notes For Permit 05082088
Permit Number 05082088
Review Stop E
Sequence Number 2
Notes
Date Text
2005-12-06 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SUBMIT TWO COMPLETE SETS
 OF PLANS, SPECS/MANUFACTURE CUT SHEETS.
 PLEASE BE SURE ALL PLANS CONTAIN THE
 PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR PLANS/ DESIGN.
 FBC 104.2.1 ADMINISTRATIVE SECTION.
  
 2)NOTE: PLEASE SEE PANEL SCHEDULE/LOAD
 CALCULATIONS SUBMITTED INDICATE FOR
 PANEL "A", HOWEVER RISER DIAGRAM SHOWS
 PANEL "B" AS THE EM PANEL?
 PLEASE CORRELATE.
  
  
 3)NOTE: PLEASE SEE LOAD CALCUALTIONS
 EXCEED RATING OF DISCONNECTS FOR
 GENERATOR AND SERVICE.
 PLEASE SEE LOAD FOR PANEL.
 215.5
  
 4)NOTE: PLEASE SEE PERMIT APPLICATION
 HAS NOW BEEN CHANGED BACK TO NATURAL
 GAS, HOWEVER PLEASE SEE SPECS FOR
 GENERATOR INDICATE THIS AS LP?
 PLEASE ALSO VERIFY WHICH, AS GEN IS NOT
 RATED AT 40KW AS NG.
 215.5
  
 ** PLEASE NOTE**
 AUTOMATIC LOAD SHEDDING MAY BE AN
 OPTION.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE ALSO BE SURE TO SUBMIT
 "2" SETS OF PLANS TOGETHER.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 ** PLEASE SEE THE NOC SHOWN IS FOR THE
 BLD CONTRACTOR AND FOR THE NEW SFR. A
 SEPARATE NOC WILL BE REQUIRED AS THE NEW
 SFR DOES NOT INCLUDE THE GENERATOR.FS
 713.13(2)
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]