Plan Review Notes
Plan Review Notes For Permit 05082088
Permit Number 05082088
Review Stop E
Sequence Number 1
Notes
Date Text
2005-09-09 00:00:00*** UNSAT ****
  
 1)NOTE:
 PLEASE SEE 230.72 FOR GROUPING OF MAINS.
 PLEASE CLARIFY IF EXSITING MCB PANEL IS
 LOCATED IMMEDIATELY AJACENT/CLOSE
 PROXIMITY TO EXISTING PANELS.
 PLEASE SEE 225.31 FOR DISCONNECTING
 MEANS REQUIRED, GROUPED PER 225.34 AND
 RATED FOR SERVICE EQUIPMENT PER 225.36
 PLEASE SEE NO SPECS/MANUFACTURE CUT
 SHEETS WERE SUBMITTED FOR ATS.
 PLEASE SEE THE REQUIRED DISCONNECT FROM
 GEN IS LOCATED ON THE OTHER SIDE OF
 HOUSE, WHICH DOES NOT GROUP MAINS.
  
 2)NOTE:
  
 3)NOTE:
  
 4)NOTE: PLEASE SEELOAD CALCULATIONS
 SUBMITTED. PLEASE SEE 220.31B, NO
 DERATING MAY BE TAKEN FOR AHU/HEAT.
 PLEASE SEE IS IT PERMITTED TO "LOAD
 SHED" HEAT LOADS FROM A/C SYSTEMS
 THROUGH LV CONTACTORS FROM GEN OR ATS.
 220.31,702.5, 90.4,700.5
 PLEASE SEE 700.58, WHICH PERMIT LOAD
 SHEDDING. PLEASE PROVIDE DETAIL IS ANY
 OF THE LV CONTACTS PROVIDE BY ATS OR GEN
 WILL BE USED TO INTERUPT ONE OR MORE
 HEAT CONTROL WIRES.
  
 5)NOTE:
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW