2005-09-20 00:00:00 
  1ST REVIEW
  ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE
 ISSUED.
  
 2) PROVIDE INFORMATION FOR THE SLAB
 AND
 ANCHORING OF GENERATOR, SEE1606.1.3
 ANCHORAGE AGAINST OVERTURNING, UPLIFT
 AND SLIDING. STRUCTURAL MEMBERS AND
 SYSTEMS, AND COMPONENTS AND CLADDING
 IN
 A BUILDING OR STRUCTURE SHALL BE
 ANCHORED TO RESIST WIND-INDUCED
 OVERTURNING, UPLIFT AND SLIDING AND TO
 PROVIDE CONTINUOUS LOAD PATHS FOR
 THESE
 FORCES TO THE FOUNDATION.WHERE A
 PORTION OF THE RESISTANCE TO THESE
 FORCES IS PROVIDED BY DEAD LOAD, THE
 MINIMUM DEAD LOAD LIKELY TO BE IN
 PLACE
 DURING A DESIGN WIND EVENT SHALL BE
 USED.
  
 3) SURVEY: FL S S472.025 REQUIRES
 SURVEYS TO BE ORIGINALS, SIGNED,
 SEALED
 AND DATED.
  
 4 ) FBC 104.2.1ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME
 AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 ANY QUESTIONS CALL ME.
  