Plan Review Notes For Permit 05082085 |
Permit Number |
05082085 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-11-07 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIW. | | | | 1} PLEASE INDICATE THE PRIME MOVER (FUEL | | TYPE). THE | | | | 2} PLEASE SEE ARTICLE 445.13, 4/0 IS TOO | | SMALL FOR 75K PLUS 115%. | | | | 3} THE GEC MUST BE LOCATED AT THTE METER | | OR THE FIRST MEANS OF DICONNECTT THE | | RISER HAS IT SHOWN AT THE ATS WHICH | | WOULD BE INCORRECT. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | | | |
|