Plan Review Notes
Plan Review Notes For Permit 05082085
Permit Number 05082085
Review Stop M
Sequence Number 1
Notes
Date Text
2005-09-15 00:00:00*** PROVISO ***
 1) PLANS MUST SHOW ANY BUILDING OPENINGS
 (WINDOWS, DOORS, ROOF & EAVE VENTS).
 2) GENERATOR EXHAUST MUST BE TEN FEET
 AWAY FROM ANY BUILDING OPENINGS
 (WINDOWS, DOORS, ROOF & EAVE VENTS), AND
 TEN FEET AWAY FROM ADJACENT BUILDING
 OPENINGS. 2001 FBC/M 804.3.3 .
 3) NATURAL GAS PIPING REQUIRES A GAS
 PERMIT APPLICATION BY A LICENSE PLUMBING
 CONTRACTOR.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.