2005-09-09 00:00:00 | *** UNSAT **** |
| |
| 1)NOTE: PLEASE SEE MAIN DISCONNECT IS |
| REQUIRED TO MANUAL AND LOCATED ON THE |
| OUTSIDE OF SERVICE EQUIPMENT. |
| 230.76,230.79 |
| PLEASE SEE 230.72 FOR GROUPING OF MAINS. |
| PLEASE CLARIFY IF EXSITING MCB PANEL IS |
| LOCATED IMMEDIATELY AJACENT/CLOSE |
| PROXIMITY TO EXISTING PANELS. |
| PLEASE SEE 225.31 FOR DISCONNECTING |
| MEANS REQUIRED, GROUPED PER 225.34 AND |
| RATED FOR SERVICE EQUIPMENT PER 225.36 |
| PLEASE SEE NO SPECS/MANUFACTURE CUT |
| SHEETS WERE SUBMITTED FOR ATS. |
| |
| 2)NOTE: PLEASE SEE RISER INDICATES AN |
| "EQUIPMENT GROUNDING" CONDUCTOR FROM |
| METER TO MAIN. 250.6, 250.24 |
| PLEASE SEE AN EQUIPMENT GRND IS ONLY |
| INSTALLED AFTER THE FIRST MEANS OF |
| DISCONNECT. |
| |
| 3)NOTE: PLEASE SEE SITE/ EQUIPMENT PLANS |
| DOES NOT INDICATE LOCATION OF ATS, |
| EXISTING MAINS, OR EXISITNG PANELS. |
| ARE EXISTING PANELS MCB? |
| |
| |
| 4)NOTE: PLEASE SEELOAD CALCULATIONS |
| SUBMITTED. PLEASE SEE 220.31B, NO |
| DERATING MAY BE TAKEN FOR AHU/HEAT. |
| PLEASE SEE IS IT PERMITTED TO "LOAD |
| SHED" HEAT LOADS FROM A/C SYSTEMS |
| THROUGH LV CONTACTORS FROM GEN OR ATS. |
| 220.31,702.5, 90.4,700.5 |
| |
| 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| |
| 6)NOTE: PLEASE VERFIY 3 OVENS SHOWN ON |
| SERVICE PANELS?? THIS IS OK, JUST A |
| NOTE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |