Plan Review Notes
Plan Review Notes For Permit 05081982
Permit Number 05081982
Review Stop B
Sequence Number 4
Notes
Date Text
2006-07-28 00:00:00DENIED
  
  
  
 1.REVISE THE PERMIT VALUE TO REFLECT
 ALL MATERIALS AND LABOR FOR THE REVISED
 WORK.ADDITIONAL PERMIT FEES ARE DUE.
  
 2.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
 TRUSS DRAWING REQUIRED TO BE APPROVED
 PRIOR TO INSTALLATION.
  
 3.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 4.WIND LOADING SHALL BE TO ASCE 7-02.
  
 5.GUARDRAILS SHALL BE DESIGNED TO FBC
 R-312.1 AND R-312.2
  
 6.PLANS REQUIRE AN HISTORICAL REVIEW
 PRIOR TO RESUBMITTING.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  