Date |
Text |
2005-09-23 00:00:00 | DENIED |
| |
| 1.NOT ENOUGH INFORMATION REQUIRED TO |
| DO A COMPLETE BUILDING REVIEW. |
| ADDITIONAL COMMENTS MAY ARISE AFTER |
| REVISED PLANS ARE SUBMITTED. |
| |
| 2.SUBMIT TWO COPIES OF ORIGONAL SIGNED |
| AND SEALED SURVEYS. INCLUDE LOCATION OF |
| NEW ROOM ADDITION ON SURVEY. FS 472.025 |
| |
| 3.INCLUDE A FLOOR PLAN SHOWING THE |
| EXISTING BUILDING AND A PLAN SHOWING THE |
| NEW WORK. |
| |
| 4.INCLUDE ON PLANS AREA CALCULATIONS |
| FOR EXISTING A/C AND NON A/C COVERED |
| AREA FOR BOTH NEW AND EXISTING. |
| |
| 5.FOOTINGS SHAL HAVE A MINIMUM DEPTH |
| OF 12" BELOW GRADE 1804.1.3 |
| |
| 6.SUBMIT ENERGY CALCS PER FBC CH. 13 |
| |
| 7.BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 8.SHOW HOW EXTERIOR WALLS WILL BE |
| SECURED FROM BOTTOM PLATE THROUGH ROOF |
| FRAMING. |
| |
| 9.NEW EXTERIOR WINDOWS REQUIRE IMPACT |
| PROTECTION.SUBMIT EITHER PRODUCT |
| APPROVALS FOR IMPACT GLASS OR SHUTTERS |
| OR A SEPERATE PERMIT FOR IMPACT |
| PROTECTION WILL BE REQUIRED. |
| |
| 10.ALL PRODUCT APPROVALS SUBMITTED |
| SHALL HAVE THE FOLLOWING STATE PRODUCT |
| APPROVAL ATTACHED. |
| PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 11.INFORMATION FOR IKO SHINGLES IS NOT |
| A PRODUCT APPROVAL.IT IS JUST A SPEC |
| SHEET AND INSTALLATION GUIDE. |
| SUBMIT TWO COPIED OF PRODUCT APPROVALS. |
| |
| 12.PRODUCT APPROVALS REQUIRED FOR |
| EXTERIOR DOORS. |
| |
| 13.SHOW HOW BUILDING WILL BE DESIGNED |
| TOFBC 1606.1.1 FOR WIND LOADS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |