Plan Review Notes For Permit 05081937 |
Permit Number |
05081937 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-09-20 00:00:00 | | | | | | | | | BUILDING REVIEW COMMENTS | | -------- ------ -------- | | | | | | | | 1] | | MIN. FINISH FLOORS AND ALL APPLIANCES | | SHALL BE NOTED TO BE ABOVE 7.5'. | | | | 2] | | GENERAL NOTES #2 IS NOT IN COMPLIANCE | | WITH SOILS ENGINEERING REQUIREMENTS. | | | | 3] | | HOW IS NEW F1 FOOTER FASTENED TO | | EXISTING STEMWALL. | | | | 4] | | PROVIDE DETAIL FOR NEW CONCRETE SLABS | | ON PAGES 3OF6 AND 5OF6. | | | | 5] | | EXPLAIN NOTE #8. | | | | 6] | | PROVIDE 2ND SET OF SIGNED AND SEALED | | DRAWINGS. | | | | | | | | | | | | | | LUIS MARTINEZ | | 805-6710 |
|