Plan Review Notes For Permit 05081889 |
Permit Number |
05081889 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-09-02 00:00:00 | *** PROVISO *** | | 1) IF SUPPLY AIR IS GREATER THAN 2000 | | CFM A SMOKE DETECTOR IS REQUIRED | | 2001 FBC/M 606.2.1. | | 2) PROVIDE FOR AUX. DRAIN PAN UNDER | | A.H.U. WITH DRAIN PROTECTION 2001 | | FBC/M 307.2.3. | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | TOM GORDON 805-6729 OR PATTY KRAUSS | | 805-6719. |
|