2005-10-14 00:00:00********** UNSAT2ND REVIEW *********
  
 PLEASE SEE MANY NOTES FROM PREVIOUS
 REVIEWWHICH STILL NEED TO BE
 ADDRESSED.
  
 1)NOTE: NOTE #1, NO, PLEASE SEE BASED ON
 SCALE PROVIDED ON PLANS, ONE GFI IS
 STILL MISSING. SEE REDLINED PLANS.
  
 2)NOTE: NOTE #2, NO, PLEASE SEE LOCATION
 OF WASHER AND DRYER NOT SHOWN ON PLANS.
 PLEASE SEE PREVIOUS RISER DID NOT
 INDICATE A PANEL "C" FOR AN APT? PLEASE
 CLARIFY IF THIS PANEL IS EXISITNG OR
 NEW.
 PLEASE CALL IF NEW AS THERE MAY BE SOME
 CODE COMMENTS. IF EXIST , ONLY IDENTIFY
 AS EXIST. PLEASE HOWEVER SEE COMMENTS
 FOR LOAD CALCULATIONS.
  
 3)NOTE: NOTE#3 OK, AS PLANS MENTIONS ALL
 A/C AS EXISTING AND NOT PROPOSED WORK TO
 BE DONE.
  
 4)NOTE: NOTE #4 OK, PLEASE KNOW, EVEN IF
 SHLEVING IS NOT IN A CLOSET, THE CODE
 TAKES INTO ACCOUNTAMIN SHELVING
 DISTANCE FROM WALLS.
 PLEASE SEE A FLOURESCENE FIXTURE ABOVE
 DOOR IS OK PER 410.8
  
 5)NOTE: NOTE#5, NO, PLEASE SEE NOTE ON
 PLANS DOES NOT INCLUDE QLL REQUIRED PER
 210.12. PLEASE ALSO SEE NOTE NOW SHOWN
 FOR SD'S INDICATES BEING CONNECTED TO A
 GFI CIRCUIT?
 PLEASE SEE ARC FAULT AND GFI ARE TWO
 DIFFERENT PROTECTION METHODS.
  
 6)NOTE: NOTE #6 OK.
  
 7)NOTE: NOTE #7 OK.
  
 8)NOTE: NOTE #8 NO,
 PLEASE SEE MIN AWG REQUIRED FOR OCP TO
 BE BASED ON 240.4,310.16.
 PLEASE SEE DRYER SHOWING 40A OCP ON #10
 AWG.
 PLEASE KNOW, NOW LOAD FOR WATER IS HSOWN
 AT 3.8 KW, HOWEVER 422.13 WHICH REQUIRES
 MIN OCP TO BE 125% AND 422.11E REQUIURES
 MAX OCP AT 150%. PLEASE KNOW AT 3.8 KW,
 40A OCP IS TOO HIGH.
  
 9)NOTE: NOTE #9, NO, PLEASE SEE 424.3B
 FOR MIN OCP FOR AHU. MIN 125%
  
 10)NOTE: NOTE #10 NO, PLEASE SEE 220.16
 FOR MIN OF 5KW TO BE SHOWN FOR DRYER.
 PLEASE SEE RESPONSEMENTIONS 5KW IS
 SHOWN, HOWEVER PANEL SCHEDULE/LOAD CALCS
 INDICATE 2.5KW.
  
 11)NOTE: NOTE #11 NO, SEE PREVIOUS NOTE
 #8 FOR WATER HEATER COMMENT.
  
 12)NOTE: NOTE #12 NO, PLEASE SEE 220 FOR
 MIN LOAD CALCULATIONS,
 PLEASE SEE CONDENSING UNIT LOAD IS NOW
 SHOWN AT 23 KVA/KW?? PLEASE VERIFY. "IF"
 A/C CU IS 23KW, THEN THE COOLING LOAD IS
 TO BE FIGURED ON LOAD CALCULATIONS AS
 THIS LOAD IS LARGER THAN HEAT. THIS
 APPEARS TO BE AMISPRINT OR INCORRECT
 ??
 PLEASE SEE LOAD FROM PANEL "C" DOES NOT
 INDICATE OF THERE IS ANY A/C LOADS?
 PLEASE SEE NEC 220 FOR MIN KW RATING FOR
 STOVE/RANGE/OVEN TO BE PER NAMEPLATE ,
 MIN 8KW.
 PLEASE SEE LOAD SHOWN FOR PANEL "B" IS
 BEING DE-RATED TWICE.
 LOAD SHALL BE FIGURED AND DE-RATED FOR
 LOAD ON PANEL "B", HOWEVER THE CONNECTED
 LOAD MUST BE SHOWN AND FIGURED WHEN
 CALCULATIONS FOR PANEL "A" ARE DONE.
  
  
 13)NOTE: NOTE #13 OK, AS PLANS NOW
 INDICATE MAIN SERVICE AS EXISTING.
  
 14)NOTE: NOTE #14 OK. ADDED.
  
 15)NOTE: NOTE #15 NO, SEE PREVIOUS NOTE
 WITH RESPECT TO CONNECTION OF SD'S.
  
 16)NOTE: NOTE #16 OK, EXISTING.
  
 17)NOTE: NOTE #17, NO, PLEASE SEE ONLY
 THE PRINTED NAME IS SHOWN ON PLANS.
 FBC 104.2.1
  
 18)NOTE: NOTE #18, NO, PLEASE KNOW,
 VALUE MUST BE BASED ON WHAT IS WOULD
 COST AT FAIR MARKET VALUE IF A
 CONTRACTOR WAS DOING THE WORK.
 104.6.5
  
 19)NOTE: PLEASE SEE FBC CHAPTER 34 WITH
 RESPECT TO REMODEL WORK FOR ELECTRICAL
 WIRING.
 PLEASE KNOW, EXSITING OTHER AREAS MAY BE
 REQUIRED TO BE BROUGHT UP TO MIN CODE,
 IF NOT ALREADY. PLANS/NOTES MENTIONS
 EXISTING AREAS HAVE ALREADY BEEN BROUGHT
 UP TO CODE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW . IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  