Date |
Text |
2005-09-02 00:00:00 | ********* UNSAT *********** |
| |
| 1)NOTE: PLEASE SEE 210.52C1 FOR SOME |
| MISSING GFI RECEPTS ALONG KITCHEN |
| COUNTERSPACE. |
| PLEASE ALSO SEE AREA IN KITCHEN AT |
| MICROWAVE LOCATION APPEARS TO BE |
| COUNTERSPACE? |
| PLEASE SEE 210.8A6 FOR ALL RECEPTS |
| SERVING KITCHEN COUNTERSPACE ARE TO BE |
| GFI /GFI PROTECTED. |
| |
| 2)NOTE: PLEASE SHOW LOCATION OF ALL |
| SERVICE EQUIPMENT AS SHOWN ON RISER. |
| PLEASE LABEL PANELS, A, B ETC. |
| PLEASE SHOW LOCATIONS OF ALL APPLIANCES |
| AS INDICATED ON PANEL SCHEDULES. |
| WASHER, DRYER, AHU, CU ETC. |
| |
| 3)NOTE: PLEASE SEE 440.11 FOR MISSING |
| DISCONNECTS FOR A/C EQUIPMENT. |
| PLEASE SEE 210.63 FOR MISSING GFI FOR |
| CU. |
| |
| 4)NOTE: PLEASE SEE 410.8 FOR MIN |
| CLEARENCE OF LT FIXTURE IN CLOSET. |
| |
| 5)NOTE: PLEASE SEE PLANS INDICATE ARC |
| FAULT PROTECTION FROM THE PREVIOUS CODE. |
| PLEASE SEE 2002 NEC 210.12, WHICH |
| REQUIRES ARC FAULT PROTECTION FOR ALL |
| OUTLETS IN BEDRMS, LTS, FANS, SD'S |
| RECEPTS ETC. |
| |
| 6)NOTE: PLEASE SEE MISSING RECEPT PER |
| 210.52 |
| |
| 7)NOTE; PLEASE SEE MISSING DEDICATED |
| BATH CIRCUIT PER 210.52D,210.11C3 MUST |
| BE 20A #12 |
| |
| 8)NOTE: PLEASE PROVIDE PANEL SCHEDULE(S) |
| SHOWING ALL MINCIRCUITS AND CORRELATE |
| WITH LOAD CALCULATIONS. |
| PLEASE SHOW ALL MIN AWG PER NEC 310.16 |
| PLEASE SEE 3-SMALL APPL CIRCUITS SHOWN |
| ON PANEL SCHEDULE, ONLY 2 SHOWN IN LOAD |
| CALCS. |
| PLEASE SEE CORRELATE ALL ITEMS ON PANEL |
| SCHEDULE(S) WITH LOADS SHOWN IN LOAD |
| CALCULATIONS. |
| (DRYER, A/C SYSTEM,, ETC |
| |
| 9)NOTE: PLEASE SEE MIN OCP FOR AHU HEAT, |
| SHALL BE SIZED PER 424.3B |
| MIN 125%. |
| |
| 10)NOTE: PLEASE SEE 220.16, MIN OF 5KW |
| SHALL BE FIGURED FOR DRYER. PLEASE SEE |
| 3.6 SHOWN. |
| PLEASE ADJUST. |
| |
| 11)NOTE: PLEASE VERIFY 2500W WATER |
| HEATER. PLEASE BE SURE THIS IS THE TOTAL |
| NAME PLATE RATING AND NOT ONLY ONE |
| ELEMENT. THISSIZE UNIT SEEMS SMALL FOR |
| A 1200 SQ FT HOUSE. |
| |
| 12)NOTE: PLEASE SEE A/C HEAT LOAD MAY |
| NOT BE DE-RATED AT 40%. PLEASE SEE |
| 220.31B FOR LOAD CALCULATIONS. |
| PLEASE SEE MIN SERVICE SHOWN MENTIONS, |
| 100A'S, HOWEVER 200A SERVICE IS SHOWN ON |
| RISER? |
| |
| 13)NOTE: PLEASE INDICATE MIN GROUNDING |
| ELECTRODE SYSTEM PER 250.50. COLD WATER |
| PIPE AND MIN OF 2-GRNDS RODS. |
| |
| 14)NOTE: PLEASE SEE MISSING EQUIPMENT |
| GROUNDING CONDUCTOR FROM MAIN TO SUB |
| PANEL. |
| PLEASE SEE 250.110 AND 250.122 FOR |
| SIZING. |
| |
| 15)NOTE: PLEASE SEE SD'S ARE BEING SHOWN |
| CONNECTED TO WHAT APPEARS TO BE LAUNDRY |
| RM LT. IF THIS THE CASE, ARC FAULT |
| PROTECTION WOULD ALSO BE REQUIRED FOR |
| THIS CIRCUIT. |
| |
| 16)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| |
| 17)NOTE: PLEASE SEE FBC 104.2.1 WHICH |
| REQUIRES THE PRINTED NAME AND SIGNATURE |
| OF THE PERSON RESPONSIBLE FOR PLANS . |
| |
| 18)NOTE: PLEASE SEE 104.6.5, VALUATION |
| FOR SCOPE OF WORK MUST BE BASED ON FAIR |
| MARKET VALUE. (CONTRACTORS PRICE) |
| INCLUDING ALL LABOR AND MATERIALS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
| |
| |
| |
| |
2005-09-01 00:00:00 | IN ELEC FOR REVIEW. |
| NOTES TO FOLLOW. |