Plan Review Notes
Plan Review Notes For Permit 05081855
Permit Number 05081855
Review Stop E
Sequence Number 1
Notes
Date Text
2005-09-02 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE SEE 210.52C1 FOR SOME
 MISSING GFI RECEPTS ALONG KITCHEN
 COUNTERSPACE.
 PLEASE ALSO SEE AREA IN KITCHEN AT
 MICROWAVE LOCATION APPEARS TO BE
 COUNTERSPACE?
 PLEASE SEE 210.8A6 FOR ALL RECEPTS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI /GFI PROTECTED.
  
 2)NOTE: PLEASE SHOW LOCATION OF ALL
 SERVICE EQUIPMENT AS SHOWN ON RISER.
 PLEASE LABEL PANELS, A, B ETC.
 PLEASE SHOW LOCATIONS OF ALL APPLIANCES
 AS INDICATED ON PANEL SCHEDULES.
 WASHER, DRYER, AHU, CU ETC.
  
 3)NOTE: PLEASE SEE 440.11 FOR MISSING
 DISCONNECTS FOR A/C EQUIPMENT.
 PLEASE SEE 210.63 FOR MISSING GFI FOR
 CU.
  
 4)NOTE: PLEASE SEE 410.8 FOR MIN
 CLEARENCE OF LT FIXTURE IN CLOSET.
  
 5)NOTE: PLEASE SEE PLANS INDICATE ARC
 FAULT PROTECTION FROM THE PREVIOUS CODE.
 PLEASE SEE 2002 NEC 210.12, WHICH
 REQUIRES ARC FAULT PROTECTION FOR ALL
 OUTLETS IN BEDRMS, LTS, FANS, SD'S
 RECEPTS ETC.
  
 6)NOTE: PLEASE SEE MISSING RECEPT PER
 210.52
  
 7)NOTE; PLEASE SEE MISSING DEDICATED
 BATH CIRCUIT PER 210.52D,210.11C3 MUST
 BE 20A #12
  
 8)NOTE: PLEASE PROVIDE PANEL SCHEDULE(S)
 SHOWING ALL MINCIRCUITS AND CORRELATE
 WITH LOAD CALCULATIONS.
 PLEASE SHOW ALL MIN AWG PER NEC 310.16
 PLEASE SEE 3-SMALL APPL CIRCUITS SHOWN
 ON PANEL SCHEDULE, ONLY 2 SHOWN IN LOAD
 CALCS.
 PLEASE SEE CORRELATE ALL ITEMS ON PANEL
 SCHEDULE(S) WITH LOADS SHOWN IN LOAD
 CALCULATIONS.
 (DRYER, A/C SYSTEM,, ETC
  
 9)NOTE: PLEASE SEE MIN OCP FOR AHU HEAT,
 SHALL BE SIZED PER 424.3B
 MIN 125%.
  
 10)NOTE: PLEASE SEE 220.16, MIN OF 5KW
 SHALL BE FIGURED FOR DRYER. PLEASE SEE
 3.6 SHOWN.
 PLEASE ADJUST.
  
 11)NOTE: PLEASE VERIFY 2500W WATER
 HEATER. PLEASE BE SURE THIS IS THE TOTAL
 NAME PLATE RATING AND NOT ONLY ONE
 ELEMENT. THISSIZE UNIT SEEMS SMALL FOR
 A 1200 SQ FT HOUSE.
  
 12)NOTE: PLEASE SEE A/C HEAT LOAD MAY
 NOT BE DE-RATED AT 40%. PLEASE SEE
 220.31B FOR LOAD CALCULATIONS.
 PLEASE SEE MIN SERVICE SHOWN MENTIONS,
 100A'S, HOWEVER 200A SERVICE IS SHOWN ON
 RISER?
  
 13)NOTE: PLEASE INDICATE MIN GROUNDING
 ELECTRODE SYSTEM PER 250.50. COLD WATER
 PIPE AND MIN OF 2-GRNDS RODS.
  
 14)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO SUB
 PANEL.
 PLEASE SEE 250.110 AND 250.122 FOR
 SIZING.
  
 15)NOTE: PLEASE SEE SD'S ARE BEING SHOWN
 CONNECTED TO WHAT APPEARS TO BE LAUNDRY
 RM LT. IF THIS THE CASE, ARC FAULT
 PROTECTION WOULD ALSO BE REQUIRED FOR
 THIS CIRCUIT.
  
 16)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 17)NOTE: PLEASE SEE FBC 104.2.1 WHICH
 REQUIRES THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR PLANS .
  
 18)NOTE: PLEASE SEE 104.6.5, VALUATION
 FOR SCOPE OF WORK MUST BE BASED ON FAIR
 MARKET VALUE. (CONTRACTORS PRICE)
 INCLUDING ALL LABOR AND MATERIALS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
2005-09-01 00:00:00IN ELEC FOR REVIEW.
 NOTES TO FOLLOW.