Plan Review Notes For Permit 05081654 |
Permit Number |
05081654 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-09-09 00:00:00 | **** UNSAT **** | | | | 1)NOTE: PLEASE SEE MAIN DISCONNECT IS | | REQUIRED TO MANUAL AND LOCATED ON THE | | OUTSIDE OF SERVICE EQUIPMENT. | | 230.76,230.79 | | PLEASE SEE 230.72 FOR GROUPING OF MAINS. | | | | 2)NOTE: PLEASE SEE RISER INDICATES AN | | "EQUIPMENT GROUNDING" CONDUCTOR FROM | | METER TO MAIN. 250.6, 250.24 | | PLEASE SEE AN EQUIPMENT GRND IS ONLY | | INSTALLED AFTER THE FIRST MEANS OF | | DISCONNECT. | | | | 3)NOTE: PLEASE SEE SITE/ EQUIPMENT PLANS | | DOES NOT INDICATE LOCATION OF ATS. | | | | 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | RATED FOR THE AVAILABLE FAULT CURRENT. | | PER 110.9/215.5 | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW AND IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|