Plan Review Notes
Plan Review Notes For Permit 05081648
Permit Number 05081648
Review Stop B
Sequence Number 1
Notes
Date Text
2005-09-16 00:00:00BUILDING REVIEW CHECKLIST:
 1- BRING PLANS BACK TO PALM BEACH COUNTY
 TO CORRECT PR NUMBERS. I TALKED TO MRS.
 GIL FROM THE COUNTY SHE SAYS THAT THIS
 IMPACT FEES RECEIPT (PR#: 05042803)
 DOESN'T MATCH THIS PROPERTY. REVISE AS
 REQUIRED. BRING BACK CORRECT PAID
 RECEIPT AND PLANS STAMPED WITH
 CORRESPONDING PR NUMBER.
  
 2- NEED RECORDED N.O.C.
  
 3- ENERGY CALCS ARE GETTING THE CEILING
 FANS CREDIT. REVISE ELECTRICAL PLAN TO
 SPECIFY CEILING FAN SIZE IN EACH ROOM
 INCLUDING CEILINGS FANS REQUIRED IN THE
 GREAT ROOM. SEE TABLE 6-6 CHAPTER 13 FBC
  
 4- REVISE ROOF FRAMING PLAN AT ENTRY
 PORCH ROOF. CONCRETE BEAM DOESN'T EXTEND
 TO THE FOYER AREA. REVISE FRAMING AROUND
 KNEEWALL ON THE LEFT HAND SIDE. THERE IS
 NOT CONCRETE BEAM. REVISE ROOF FRAMING
 PLAN AS REQ'D AND SPECIFY CORRESPONDING
 CONNECTORS. SEC. 104.2.1.2 CITY
 AMENDEMNTS TO FBC 2001.
  
 5- MULLION SIZE SPECIFIED FOR FIXED
 WINDOWS AT GREAT ROOM AREA DOESN'T
 RESIST THE DESIGN PRESSURES. REVISE AS
 REQ'D. SEC. 104.2.1.2 CITY AMENDMENTS TO
 FBC.
  
 6- TRUSS ANCHOR SCHEDULE: REVISE NUMBER
 OF NAILS FOR HUS26. SEE 2005 CATALOGUE.
  
 7- PROVIDE PRODUCT APPROVAL FOR:
 A) "INSWING" 1HR FIRE RATED DOOR AT
 ATRIUM AS SHOWN ON PLANS.
  
 B) MULLION SIZE SPECIFIED FOR FIXED
 WINDOWS AT GREAT ROOM AREA.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.