2006-05-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEWS:
  
 1. SHTS P2.1.1, P2.1, P3.1.1, & P3.1,
 UNDERGROUND DRAINAGE PIPING PARALLEL
 WITH THE FOOTER SHALL COMPLY WITH
 SECTION 307.4. BUILDING DRAIN SHOULD BE
 MOVED AWAY FROM THE FOOTERS. "OUT OF THE
 MONOLITHIC FOOTER". (MINIMUM 4' FROM
 BLOCK WALL).
  
 **************NEW COMMENTS**************
 1B. SHTS P2.2, P2.3, P2.3.2, P3.2,
 P3.2.4, P3.3, P3.3.1, P3.3.2, & P4.1 THE
 INFORMATION REQUIRED ON THE SEAL IS NOT
 BEING IMPRESSED ON THE SHEET AS REQUIRED
 IN FAC 61G15-23.002 & FS 471.025.-
 THE ENGINEER SHALL SIGN HIS/HER NAME.
 THE INITIALS ARE NOT ACCEPTABLE AND DO
 NOT APPEAR TO MATCH THE SIGNATURE ON THE
 OTHER SHEETS. FAC 61G15-23.002(1) & FS
 471.025.(ONE SET OF PLUMBING SHEETS
 WILL BE WITH-HELD FOR POSSIBLE REVIEW BY
 DBPR).-NEW SEAL WITH "LICENCE"
 REQUIRED ON ALL SHEETS SEALED AFTER DEC.
 31, 2005 PER THE LETTER FROM THE FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]