Plan Review Notes
Plan Review Notes For Permit 05081350
Permit Number 05081350
Review Stop M
Sequence Number 3
Notes
Date Text
2006-06-06 00:00:00PROVISO:2001 FBC/BUILDING 6/6 UNITS
  
 PLEASE REVISE PLANS TO REFLECT THE
 IMPLEMENTATION OF THE PROVISO'S.
  
 1.THE FIRST FLOOR MECHANICAL PLAN (M1)
 DOES NOT MATCH THE FIRST FLOOR
 ARCHITECTURAL PLAN (A-2.0.1).PLEASE
 NOTE, RETURN AIR BETWEEN THE GARAGE DOOR
 & THE FOYER DOOR IS NOT REQURIED PER
 2001 FMC 601.4 EXCEPTION #3, R/A IS ONLY
 REQUIRED FROM HABITABLE SPACES.
  
 2.PLAN SHEET M0.1 THE AHU MOUNTING
 DETAIL NOTE 15 STATES, "NO COMBUSTIBLES
 ALLOWED IN THE MECHANICAL CLOSET" AS
 THIS SERVES AS A RETURN AIR PLENUM.THE
 DOOR SCHEDULE ON PLAN SHEET A-4.1.1
 INDICATES THE AHU CLOSET DOOR AS A WOOD
 LOUVERED DOOR.PLEASE VERIFY WITH THE
 DOOR MANUFACTURE THAT THIS WILL MEET THE
 REQUIRED 25 FLAME/50 SMOKE INDEX AS
 SPECIFIED IN 2001 FMC 602.2.1.
  
 3.OUTSIDE AIR CALCULATIONS INDICATED
 ON PLAN SEET M0.1 ARE BASED ON
 INFLITRATION RATES.THE INFILTRATION
 RATES ARE THE "MAXIMUM" ALLOWED BY CODE
 & MAY NOT BE A "TRUE/ACTUAL" RATE.
 PLEASE PROVIDE CALCS IN ACCORDANCE WITH
 2001 FMC 402.2, 402.2.1 OR TABLE 403.3.
 PLEASE NOTE, 6" O.A. DUCT IS INDICATED
 ON M2.PLEASE REMOVE FROM THE PLAN IF
 THIS DUCT WILL NOT BE INSTALLED.
  
 4.SPECIFIC DRYERS ARE TO BE INSTALLED
 BY FINAL INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.