2006-06-06 00:00:00 | PROVISO:2001 FBC/BUILDING 6/6 UNITS |
| |
| PLEASE REVISE PLANS TO REFLECT THE |
| IMPLEMENTATION OF THE PROVISO'S. |
| |
| 1.THE FIRST FLOOR MECHANICAL PLAN (M1) |
| DOES NOT MATCH THE FIRST FLOOR |
| ARCHITECTURAL PLAN (A-2.0.1).PLEASE |
| NOTE, RETURN AIR BETWEEN THE GARAGE DOOR |
| & THE FOYER DOOR IS NOT REQURIED PER |
| 2001 FMC 601.4 EXCEPTION #3, R/A IS ONLY |
| REQUIRED FROM HABITABLE SPACES. |
| |
| 2.PLAN SHEET M0.1 THE AHU MOUNTING |
| DETAIL NOTE 15 STATES, "NO COMBUSTIBLES |
| ALLOWED IN THE MECHANICAL CLOSET" AS |
| THIS SERVES AS A RETURN AIR PLENUM.THE |
| DOOR SCHEDULE ON PLAN SHEET A-4.1.1 |
| INDICATES THE AHU CLOSET DOOR AS A WOOD |
| LOUVERED DOOR.PLEASE VERIFY WITH THE |
| DOOR MANUFACTURE THAT THIS WILL MEET THE |
| REQUIRED 25 FLAME/50 SMOKE INDEX AS |
| SPECIFIED IN 2001 FMC 602.2.1. |
| |
| 3.OUTSIDE AIR CALCULATIONS INDICATED |
| ON PLAN SEET M0.1 ARE BASED ON |
| INFLITRATION RATES.THE INFILTRATION |
| RATES ARE THE "MAXIMUM" ALLOWED BY CODE |
| & MAY NOT BE A "TRUE/ACTUAL" RATE. |
| PLEASE PROVIDE CALCS IN ACCORDANCE WITH |
| 2001 FMC 402.2, 402.2.1 OR TABLE 403.3. |
| PLEASE NOTE, 6" O.A. DUCT IS INDICATED |
| ON M2.PLEASE REMOVE FROM THE PLAN IF |
| THIS DUCT WILL NOT BE INSTALLED. |
| |
| 4.SPECIFIC DRYERS ARE TO BE INSTALLED |
| BY FINAL INSPECTION. |
| |