2006-02-04 00:00:00 | PLUMBING PLAN REVIEW EXAMINER | | PAUL SCHMITZ 561-805-6692 | | [email protected] | | FBC PLUMBING 2001 | | FBC FUEL GAS 2001 | | DENIED | | 1) PLEASE ADDRESS PREVIOUS NOTES. | | BY JOHN LEECH DATED 11-19-05 | | | | 2.U/G DRAINAGE PIPE PARALLEL TO THE | | FOOTER MUST COMPLY WITH SECTION 307.4. | | BUILDING DRAIN SHOULD BE MOVED AWAY FROM | | FOOTERS. | | "OUT OF THE MONOLITHIC FOOTER." | | | | 3.WATER HEATER RELIEF VALVE DISCHARGE. | | SHT P0.1 (WATER HEATER DETAIL) SHOWS | | DISCHARGE TO GARAGE FLOOR. PAGE P2.1 | | (FLAT DRAWING) SHOWS P & T DISCHARGE TO | | OUTSIDE. REFERE TO SEC.504.7.1. REVISE | | PLANS. | | "CORRELATE SHT P0.1 WITH P2.1 SHOW | | METHOD, NOT THE CODE SECTION." |
|