Plan Review Notes For Permit 05081350 |
Permit Number |
05081350 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-02-14 00:00:00 | DENIED:BUILDING #6 / 6 UNITS | | PLEASE REFERENCE COMMENTS FROM REVIEW | | DATED 9-28-05, SINCE A RESPONSE SHEET | | WAS NOT SUBMITTED & FOR CONSISTENCY THE | | SAME NUMBER SEQUENCE WILL BE USED. | | | | 1.COMMENT ADDRESSED | | | | 2.PLAN SHEET A-0.0.0, PROJECT | | INFORMATION; PLEASE INDICATE WHAT TYPE | | OF SPRINLERED SYSTEM WILL BE INSTALLED | | I.E. 13, 13D, 13R? | | | | 3.COMMENT ADDRESSED. | | | | 4.PLAN SHEET A-10.2.0 INDICATES FIRE | | RATED ASSEMBLIES.DETAIL #5 SHOWS A 1 | | HR FIRE RATED FLOOR/CEILING ASSEMBLY. | | PLEASE INDICATE WHAT EDITION OF THE UL | | BOOK THIS ASSEMBLY WAS TAKEN FROM? THE | | DETAIL #6 FOR THE DUCT PENETRATION DOES | | NOT ADDRESS THE MEMBRANE PENETRATION | | WHERE THE DUCT & GRILLES ARE LOCATED | | BETWEEN THE RATING OF THE FLOOR/CEILING | | ASSEMBLY.PLEASE CLARIFY.PLESE NOTE | | DETAIL #1 & 2 ARE PENETRATIONS THROUGH | | CONCRETE FLOOR OR WALL ASSEMBLY. PLEASE | | PROVIDE DETAIL FOR THE WOOD FLOOR | | SYSTEM. | | | | 5 THROUGH 10COMMENTS ADDRESSED. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|