Plan Review Notes
Plan Review Notes For Permit 05081350
Permit Number 05081350
Review Stop E
Sequence Number 2
Notes
Date Text
2006-01-20 00:00:00************** UNSAT 2ND REVIEW ********
  
 **PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE ALSO SEE SOME NEW NOTES DUE TO
 CHANGES IN PLANS.
  
  
 SUB 1)NOTE: PLEASE SEE PREVIOUS NOTE
 WITH RESPECT TO THE 2003 NFPA-101 BEING
 ADOPTED AS OF JAN 1ST,2005, HOWEVER
 PLANS ARE STILL SHOWING 2002 EDITION.
 PLEASE SEE ALL PLANS, A-SHEETS AND
 ELECTRICAL SHEETS SHOULD REFERENCE
 CURRENT CODES IN EFFECT.
 PLEASE LIST THE 2002 NFPA-72, 2003
 NFPA-101, AND THE 2002 NFPA-72.
 PLEASE ALSO SEE A-0.00
  
  
  
  
 1)NOTE: NOTE #1 OK, HOWEVER SEE NEW
 NOTES DUE TO NEW SERVICE FOR BLDG BEING
 SHOWN. SEE NEW NOTES LISTED SEPARATELY
 BELOW.
  
  
 2)NOTE: NOTE #2 NO:
 ** PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 AIC RATINGS ARE SHOWN FOR EACH PANEL,
 BUT WILL ALSO BE REQUIRED FOR MAINS.(NEW
 SERVICE).
 PLEASE SEE CALCUALTIONS SUBMITTED ARE
 BASED ON UNIT MAINS, WHICH ARE OK,
 HOWEVER PLEASE SEE THE MAIN IS ALSO
 REQUIRED. THE SEC'S ARE NOT 2/0'S.
  
  
 3)NOTE: NOTE #3 OK, RECEPT RELOCATED.
  
 4))NOTE: NOTE #4 OK, CORRECTED.
  
 5)NOTE: NOTE #5 OK.
  
 6)NOTE: NOTE #6 OK.
  
 7)NOTE: NOTE #7 NO, ??PLEASE SEE THIS
 COULD NOT BE LOCATED ON LOAD CALCS.
 PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS NEEDS
 TO BE SHOWN ABOVE THE GEN. KT/RECEPT
 LOADS. THIS SHOULD BE ABOVE THE FIGURED
 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 8)NOTE: NOTE #8 NO, PLEASE SEE AN EFFORT
 WAS MADE TO LIST THESE, HOWEVER PLEASE
 SEE LISTING INDICATES "GFI" WHEREAS
 "AFCI" PROTECTION IS REQUIRED.
  
 ** PLEASE LIST ALL THE REQUIRD ARC
 FAULT PROECTED CIRCUITS AS REQUIRED PER
 2002 210.12
 PLEASE KNOW, SD'S ARE BEING SHOWN
 CIRCUITED TO KITCHEN LIGHTING CIRCUIT,
 THIS IS OK, HOWEVER PLEASE KNOW, THIS
 WOULD ALSO REQUIRE ARC FAULT PROTECTION
 FOR THIS ADDITIONAL CIRCUIT.
 THIS IS ONLY A NOTE:
  
 9)NOTE: NOTE #9 OK, NOTE WAS ADDED TO
 PLANS, HOWEVER PLEASE SEE SD'S ARE STILL
 BEING SHOWN WITHIN 20' OF COOKING
 APPLIANCES. THIS IS PERMITTED, HOWEVER
 PLEASE SPECIFY THE SD TO BE INSTALLED IN
 ORDER TO MEET EXCEPTION AS LISTED.
  
 **PLEEASE SEE NFPA-72 (2002)
 EDITION,11.8.3.5.
 PLEASE PLACE NOTE ON PLANS WHICH STATES
 LOCATIONS OF SD'S TO BE A MIN OF 3' FROM
 BATH(S) AND KITCHEN DOORS AND 20' FROM
 KITCHEN COOKING APPLIANCES.
 ** PLEASE SEE EXCEPTION TO 20' FROM
 COOKING WITH TYPE OF SD USED.**
 PLEASE SEE PLANS SHOWS A SD IN KITCHEN
 AREA AT THIS TIME.
  
 10)NOTE: NOTE #10 OK, REMOVED.
  
 11)NOTE: NOTE #11 NO.
 THIS IS REQUIRED ON ALL SHEETS.
  
 **PLEASE SEE ARCHITECTS TITLE
 BLOCK SHALL ALSO CONTAIN THE PRINTED
 LICENSE NUMBER FOR ARCHITECT OF RECORD.
 FAC 61G1-16.004.
 PLEASE SEE THIS COMMENT IS FOR ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
 PLEASE KNOW THIS COMMENT DOES NOT APPLY
 TO KAMM CONSULTING'S TITLE BLOCK.
  
 ********** NEW NOTES *************
  
 1)NOTE: PLEASE SEE 250.66 FOR MIN
 GROUNDING ELECTRODE CONDUCTOR REQUIRED.
 #4 AWG SHOWN, MIN 3/0 AWG.
  
 2)NOTE: PLEASE SEE CONDUITS FROM FPL IS
 SHOWING AN "EQUIPMENT GROUNDING
 CONDUCTOR" TO THE METER CENTER. PLEASE
 SEE 250.6,250.24.
 AN "EQUIPMENT GROUNDING CONDUCTOR" IS
 ONLY INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
 PLEASE REMOVE.
  
 3)NOTE: PLEASE INDICATE THE OCP AT THE
 METER CENTER FOR ALL UNIT BRKRS.215.5
  
 4)NOTE: PLEASE SHOW SERVICE ON PLANS.
 PLEASE SEE ELECTRICAL PLANS DO NOT
 INDICATE THE LOCATION OF SERVICE ON
 EITHER END OF BLDG. PLEASE ALSO NEEDS TO
 BE SHOWN ON THE A-SHEETS, FLR PLANS,
 ELEVATION.
  
 5)NOTE: PLEASE SEE PLANS SHALL CONTAIN
 THE SIGNATURE OF THE ENGINEER OF RECORD.
 PLEASE SEE NEW SHEETS CONTAIN "INITIALS"
 ONLY AND DO NOT CORRELATE WITH THE
 ORIGINAL PLANS.
 FS 471.025, FAC 61G15-23.002
 PLEASE SEE THIS IS REQUIRED FOR ALL
 SHEETS AND FOR ALL TRADES. PLEASE SEE
 PLUMB SHEETS WHICH ARE ALSO INITIALED.
 PLEASE SEE "RAISED SEAL" SHALL BE CLEAR
 AND VISABLE WITH ALL INFORMATION ON
 SIADE SEAL. PLEASE SEESHEETS,
 INFORMATION ON SEAL IS NOT VISABLE EVEN
 WHEN "SHADOWED WITH PENCIL".
  
 PLEASE SEE ANY OTHER POSSIBLE COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved