Plan Review Notes
Plan Review Notes For Permit 05081350
Permit Number 05081350
Review Stop B
Sequence Number 2
Notes
Date Text
2006-02-28 00:00:00DENIED
  
 1) THE 2001 FBC DOES NOT ALLOW HEIGHT OR
 AREA INCREASES FOR NFPA 13R SPRINKLER
 SYSTEMS. SEE FBC TABLE 500 FOOTNOTE (D).
 FBC 903.2 REQUIRES A NFPA 13 SPRINKLER
 SYSTEM.
  
 2) THE DOOR TO THE EXIT STAIRS AT THE
 SECOND FLOOR MUST PROVIDE A 32" CLEAR
 OPENING FROM THE FACE OF THE DOOR TO THE
 STOP WITH THE DOOR OPEN 90 DEGREES. SEE
 FBC 1003.2.1 AND 1003.2.2. THE 2-8 DOOR
 SPECIFIED DOES NOT COMPLY.
  
 3) SHOW COMPLIANCE WITH FBC MECH. TABLE
 403.3 FOR THE REQUIRED OUTDOOR AIR
 VENTILATION AT GARAGES OF 100 CFM PER
 CAR.
  
 4) SEE MECHANICAL COMMENTS FOR DUCT
 PENETRATIONS THROUGH FIRE RATED
 ASSEMBLIES.
  
 5) THE TRUSS LAYOUT AND DRAWINGS ARE ARE
 REQUIRED TO BE REVIEWED AND APPROVED BY
 THE DESIGNER OF RECORD FOR THE
 STRUCTURE. IF ACCEPTABLE, THE STRUCTURAL
 ENGINEER SHOULD STAMP AND SIGN THE TRUSS
 LAYOUT AS SUCH.
  
 6) THE TRUSS DRAWING INDEX SHEET IS
 INCOMPLETE. SEE FAC 61G15-31.003. THE
 NAME OF THE AUTHORITY HAVING
 JURISDICTION, THE LOADS AND NAME & DATE
 OF THE APPLICABLE BUILDING CODE IS
 REQUIRED.
  
 7) THE UPLIFT PRESSURES IN THE TRUSS
 ANCHOR SCHEDULE ARE INCORRECT FOR THE
 SIMPSONHETAL 12 AND THE USP USC. THE
 CORRECT UPLIFTS ARE 1265# FOR THE HETAL
 12 AND 11,150 FOR THE USC WITH 4 BOLTS
 PER 2005 CATALOGS. THESE ARE THE VALUES
 THAT DO NOT INCLUDE A STRESS INCREASE
 FOR THE STEEL CALULATIONS.
  
 8) THE STATE PRODUCT APPROVALS SUBMITTED
 FOR THE TRUSS CONNECTORS DO NOT LIST ALL
 THE CONNECTORS THAT ARE LISTED IN THE
 TRUSS ANCHORS SCHEDULE.
  
 9) SUBMIT STATE PRODUCT APPROVALS FOR
 THE 3/4 HOUR FIRE RATED 6 PANEL DOOR AT
 THE ENTRY. DOOR #1 IN THE SCHEDULE.
  
 10) THE MIAMI-DADE NOA FOR THE SINGLE
 HUNG WINDOWS HAS THE INSTALLATION
 DRAWINGS FOR THE FIXED GLASS WINDOWS
 ATTACHED. PLEASE REMOVE AND ATTACH THE
 CORRECT DRAWINGS.
  
 11) THE DECORATIVE SHUTTERS ARE REQUIRED
 TO BE APPLIED FOR UNDER A SEPARATE
 PERMIT.
  
 12)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714