2005-11-19 00:00:00 | DENIED; |
| 1.GUTTERS AND DOWN SPOUTS; SHOW |
| CALCULATIONS AND SIZES PER FBC PLUMBING |
| CHAPTER 11. |
| 2.U/G DRAINAGE PIPE PARALLEL TO THE |
| FOOTER MUST COMPLY WITH SECTION 307.4. |
| BUILDING DRAIN SHOULD BE MOVED AWAY FROM |
| FOOTERS. |
| 3.WATER HEATER RELIEF VALVE DISCHARGE. |
| SHT P0.1 (WATER HEATER DETAIOL) SHOWS |
| DISCHARGE TO GARAGE FLOOR. PAGE P2.1 |
| (FLAT DRAWING) SHOWS P & T DISCHARGE TO |
| OUTSIDE. REFURE TO SEC.504.7.1. REVISE |
| PLANS. |
| 4.BACKFLOW PROTECTION FOR EACH BUILDING |
| IS REQUIRED. PLEASE ADD NOTE TO |
| DRAWINGS. |
| 5.SHOW HOW THERMAL EXPANTION WILL BE |
| CONTROLLED. SEC. 607.3 THRU 606.3.2. |
| 6.SHOW SHUTOFF VALVE FOR WATER HEATER ON |
| RISER DIAGRAMS. |
| 7.SHOCK ARRESTORS TO BE INSTALLED PER. |
| MANUFACTURES INSTALLATION INSTUCTIONS, |
| AS CLOSE TO THE SOURCE OF HAMMER IN A |
| DIRECT LINE. |
| 8.WATER RISER DIAGRAMS (FIRST FLOOR) |
| CHANGE 1/2" HOT TO 3/4" HOT. SECOND |
| FLOOR WATER RISERS SHOW 3/4" UP FROM |
| FIRST FLOOR. |
| 9.SHOCK ARRESTORS ARE REQUIRED ON W/M'S |
| SEC. 604.9. SHOW ON WATER RISER |
| DIAGRAMS. |
| 10.SHOW CLEANOUT ON WASHER STACK AT 48" |
| A.F.F. SO W/M DOES NOT HAVE TO BE MOVED |
| IF CLEANING IS REQUIRED. |
| 11.ALL THIRD FLOOR SAN. RISER DIAGRAMS; |
| OFFSET VENT THRU ROOF AND ADD A NOTE. NO |
| PENATRATIONS THRU FIRE RESISTANT |
| PLYWOOD. SEE PAGE S-2 NOTE 2. |
| 12.PAGE P3.2.4 FLAT DRAWING UNIT B |
| OPTION 5 REVERSE, W/M VENTNOT PER RISER |
| DIAGRAM (MARKED IN RED ON ON SET OF |
| PLANS) |
| PLUMBING PLAN REVIEW BY |
| JOHN LEECH |
| 805-6695 |