Plan Review Notes
Plan Review Notes For Permit 05081350
Permit Number 05081350
Review Stop P
Sequence Number 1
Notes
Date Text
2005-11-19 00:00:00DENIED;
 1.GUTTERS AND DOWN SPOUTS; SHOW
 CALCULATIONS AND SIZES PER FBC PLUMBING
 CHAPTER 11.
 2.U/G DRAINAGE PIPE PARALLEL TO THE
 FOOTER MUST COMPLY WITH SECTION 307.4.
 BUILDING DRAIN SHOULD BE MOVED AWAY FROM
 FOOTERS.
 3.WATER HEATER RELIEF VALVE DISCHARGE.
 SHT P0.1 (WATER HEATER DETAIOL) SHOWS
 DISCHARGE TO GARAGE FLOOR. PAGE P2.1
 (FLAT DRAWING) SHOWS P & T DISCHARGE TO
 OUTSIDE. REFURE TO SEC.504.7.1. REVISE
 PLANS.
 4.BACKFLOW PROTECTION FOR EACH BUILDING
 IS REQUIRED. PLEASE ADD NOTE TO
 DRAWINGS.
 5.SHOW HOW THERMAL EXPANTION WILL BE
 CONTROLLED. SEC. 607.3 THRU 606.3.2.
 6.SHOW SHUTOFF VALVE FOR WATER HEATER ON
 RISER DIAGRAMS.
 7.SHOCK ARRESTORS TO BE INSTALLED PER.
 MANUFACTURES INSTALLATION INSTUCTIONS,
 AS CLOSE TO THE SOURCE OF HAMMER IN A
 DIRECT LINE.
 8.WATER RISER DIAGRAMS (FIRST FLOOR)
 CHANGE 1/2" HOT TO 3/4" HOT. SECOND
 FLOOR WATER RISERS SHOW 3/4" UP FROM
 FIRST FLOOR.
 9.SHOCK ARRESTORS ARE REQUIRED ON W/M'S
 SEC. 604.9. SHOW ON WATER RISER
 DIAGRAMS.
 10.SHOW CLEANOUT ON WASHER STACK AT 48"
 A.F.F. SO W/M DOES NOT HAVE TO BE MOVED
 IF CLEANING IS REQUIRED.
 11.ALL THIRD FLOOR SAN. RISER DIAGRAMS;
 OFFSET VENT THRU ROOF AND ADD A NOTE. NO
 PENATRATIONS THRU FIRE RESISTANT
 PLYWOOD. SEE PAGE S-2 NOTE 2.
 12.PAGE P3.2.4 FLAT DRAWING UNIT B
 OPTION 5 REVERSE, W/M VENTNOT PER RISER
 DIAGRAM (MARKED IN RED ON ON SET OF
 PLANS)
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 805-6695