2005-09-28 00:00:00 | DENIED: |
| 1.THE ENERGY CALCULATIONS INDICATE |
| 'SINGLE FAMILY' & PLAN SHEET A-0.0.0, |
| INDICATES OCCUPANCY CLASSIFICATION AS |
| GROUP R2, MULTI-FAMILY.ENERGY |
| CALUCALTIONS SHOULD REFLECT |
| MULTI-FAMILY. |
| |
| 2.PLAN SHEET A-0.0.0, PROJECT |
| INFORMATION; TABLE 500 THE TYPE OF |
| CONSTRUCTION IS LISTED AS TYPE VI, |
| UNPROTECTED, SPRINKLERED.PER 2001 FBC |
| TABLE 500 NOTE D; HEIGHT INCREASES NOT |
| PERMITTED IN APPLICATIONS UTILIZING NFPA |
| 13R SYSTEMS. |
| |
| 3.PLAN SHEETS A-4.0.2 THROUGH A-4.5.3 |
| NOTE #25 1-HOUR RATED CHASE REFER TO |
| DETAIL 11/A-13 (AT LIVE WORK OPTION |
| ONLY).PLEASE CLARIFY IF THE INTENT IS |
| FOR FUTURE 'LIVE WORK' UNITS. |
| |
| 4.PLAN SHEET A-10.2.0 INDICATES FIRE |
| RATED ASSEMBLIES.DETAIL #5 SHOWS A 1 |
| HOUR FIRE RATED FLOOR/CEILING ASSEMBLY. |
| PLEASE PROVIDE A DETAIL FOR THE DUCT |
| PENETRATIONS.PLEASE NOTE, PER 2001 |
| FBC(M)607.4 DUCTS EXTENDING THROUGH MORE |
| THAN ONE FLOOR SHALL BE PROTECTED BY A |
| SHAFT ENCLOSURRE.PROVIDE UL DESIGN # |
| FOR DUCT PENETRATIONS. |
| |
| 5.PLAN SHEET M1, CONDENSING UNIT SLAB |
| SHALL BE A MINIMUM OF 3 1/2" AND EXTEND |
| A MINIMUM OF 2" ABOVE THE ADJOINING |
| GRADE. |
| |
| 6.PLAN SHEET M3 UNIT A OPT.7, TRANSFER |
| GRILLE FROM THE MASTER SUITE IS NOT |
| SIZED PROPERLY.PER 2001 FBC(M)601.4 |
| EXCEPTION #2 & 3, TO ACHIEVE PROPER AIR |
| BALANCE TRANSFER GRILLES SHALL USE 50 SQ |
| INCHES OF GRILLE AREA TO 100 CFM OF |
| SUPPLY AIR.ALL AIR INTO THE MASTER |
| SUITE IS TO BE INCLUDED.PLAN INDICATES |
| 375 CFM INTO THE MASTER SUITE THEREFOR |
| THE TRANSFER GRILLE SHALL HAVE A MINIMUM |
| OF 187.5 SQ INCHES OF GRILLE AREA.DOOR |
| SHALL HAVE A 1" UNDERCUT.PLEASE REVISE |
| PLANS ACCORDINGLY. |
| |
| 7.PLEASE PROVIDE OUTSIDE AIR |
| CALUCLATIONS IN ACCORDANCE WITH 2001 |
| FBC(M) 402.2, 402.2.1 OR TABLE 403.3. |
| |
| 8.PLEASE PROVIDE DETAIL FOR THE |
| HANGING OF THE AHU LOCATED AT THE 2ND |
| FLOOR CEILING. |
| |
| 9. AUXILIARY DRAIN PAN WITH OVERFLOW |
| PROTECTION REQUIRED PER 2001 FBC(M) |
| 307.2.3. |
| |
| 10. ELECTRICAL PLANS INDICATE A 'DRYER |
| BOOSTER FAN'.THIS WILL HAVE TO BE |
| SUBMITTED TO THE BUILDING OFFICIAL AS |
| ALTERNATE MATERIALS AND METHODS |
| (AMMENDED 2001 FBC SECTION 103.7). |
| PLEASE PROVIDE LETTER FROM THE ENGINEER |
| OF THE DRYER MANUFACTURER APPROVING THE |
| INSTALLATION OF THE BOOSTER FAN WITHOUT |
| VOIDING THE WARRANTY OF THE DRYER. |
| |