2005-10-17 00:00:00 | *** NOTE ADDED *** |
| |
| |
| PLEASE KNOW, AS OF JAN 1ST, 2005, WE ARE |
| NOW UNDER THE 2003 NFPA-101. |
2005-09-04 00:00:00 | *************************************** |
| |
| PLEASE BEAR IN MIND CODES CHANGES AS OF |
| OCTOBER 1, 2005 WILL TAKE AFFECT. |
| ONLY PROJECTS/BUILDING PERMITS SUBMITTED |
| BEFORE SUCH DATE WILL FALL UNDER PRESENT |
| CODE. |
| THIS WILL NOT AFFECT ELECTRICAL CODE |
| CHANGE, AS 2005 NEC IS NOT SCHEDULED FOR |
| ADOPTION UNTIL OCT 1ST, 2006. |
| |
| *************************************** |
| |
| |
| |
| ********* UNSAT ********* |
| |
| 1)NOTE: PLEASE SEE PROJECT IS SUBMITTED |
| AS CONDO'S YET ELECTRICALSERVICES |
| PROVIDED IS SHOWN AS EACH WOULD BE A |
| TOWNHOUSE (FEE SIMPLE). |
| PLEASE SEE WATER SERVICE SHOWS |
| MULTI-FAMILY BLDG. |
| PLEASE KNOW, IF THESE AS MULTI-FAMILY |
| CONDO BLDGS; ONE SERVICE FOR EACH BLDG |
| IS PERMITTED,230.2,230.70MAINS WILL BE |
| REQUIRED TO BE GROUPED PER 230.72. |
| MCB'S SHOWN IN EACH GARAGE PANEL IS |
| PERMITTED. |
| PLEASE ADJUST SERVICE FOR BLDG. |
| |
| 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| AIC RATINGS ARE SHOWN FOR EACH PANEL, |
| BUT WILL ALSO BE REQUIRED FOR MAINS.(NEW |
| SERVICE). |
| |
| 3)NOTE: PLEASE CLARIFY LOCATION OF |
| DISHWASHER RECEPT. APPEARS TO BE SHOWN |
| BEHIND UNIT? THIS IS ONLY A NOTE: |
| |
| 4))NOTE: PLEASE SEE RECEPTS SERVING |
| KITCHEN COUNTERSPACE TO MEET 210.52C- |
| SEC'S 1,2,3,4 AND 5 |
| PLEASE SEE PLANS REDLINED FOR SOME |
| MISSING W/IN 2' OF THE END OF A COUNTER |
| OR 4' SPACING. |
| UNIT "A"/STANDARD 2FLR,,, |
| |
| 5)NOTE: PLEASE SHOW OUTLET SPACING PER |
| 210.52. 2',6`,12` RULE. |
| PLEASE SEE THESE HAVE BEEN REDLINED AT |
| LOCATIONS OF NOTES. |
| UNIT "B",3RD FLR OPT 6 2'OF WALL, UNIT |
| "A"2ND FLR, WALL APPEARS TO BE OVER 12'? |
| PLEASE SEE A COUPLE OF OTHER LOCATIONS. |
| |
| 6)NOTE: PLEASE SEE LOCATION OF A |
| RECESSED LT FIXTURE IN CLOSET |
| WASHER/DRYER LOCATION. THESE LOCATIONS |
| TYPICALLY CONTAIN SHELVING ABOVE THE |
| WASHER/DRYER'S. PLEASE SEE 410.8 FOR MIN |
| CLEARENCE FROM LT AND FIXTURE TYPES. |
| (WALL MOUNT)? AS SHOWN IN OTHER CLOSETS? |
| |
| 7 )NOTE: PLEASE SEE 220.3B4. |
| PLEASE SHOW ALL RECESSED LTS BASED ON |
| MAX WATTAGE FOR FIXTURE(S). THIS NEEDS |
| TO BE SHOWN ABOVE THE GEN. KT/RECEPT |
| LOADS. THIS SHOULD BE ABOVE THE FIGURED |
| 3W/PER SQ FT. |
| PLEASE PROVIDE FIXTURE INFORMATION ON |
| LEGEND. |
| |
| 8)NOTE: PLEASE LIST ALL THE REQUIRD ARC |
| FAULT PROECTED CIRCUITS AS REQUIRED PER |
| 2002 210.12 |
| PLEASE KNOW, SD'S ARE BEING SHOWN |
| CIRCUITED TO KITCHEN LIGHTING CIRCUIT, |
| THIS IS OK, HOWEVER PLEASE KNOW, THIS |
| WOULD ALSO REQUIRE ARC FAULT PROTECTION |
| FOR THIS ADDITIONAL CIRCUIT. |
| THIS IS ONLY A NOTE: |
| |
| 9)NOTE: PLEEASE SEE NFPA-72 (2002) |
| EDITION,11.8.3.5. |
| PLEASE PLACE NOTE ON PLANS WHICH STATES |
| LOCATIONS OF SD'S TO BE A MIN OF 3' FROM |
| BATH(S) AND KITCHEN DOORS AND 20' FROM |
| KITCHEN COOKING APPLIANCES. |
| ** PLEASE SEE EXCEPTION TO 20' FROM |
| COOKING WITH TYOE OF SD USED.** |
| PLEASE SEE PLANS SHOWS A SD IN KITCHEN |
| AREA AT THIS TIME. |
| |
| 10)NOTE: PLEASE SEE MECHANICAL NOTES |
| PERTAINING TO "DRYER BOOSTER FANS". |
| AS PER MECHANICAL THESE MAY NOT BE |
| PERMITTED AND ANY COMMENT THEY MAY HAVE |
| WILL DIRECTLY AFFECT ELECTRICAL PLANS. |
| THIS IS A NOTE, AS IT IS NOT AN NEC |
| ISSUE. |
| PLEASE SEE ALL SYSTEMS DO HAVE BE |
| LISTED.110.3,90.7 |
| |
| 11)NOTE: PLEASE SEE ARCHITECTS TITLE |
| BLOCK SHALL ALSO CONTAIN THE PRINTED |
| LICENSE NUMBER FOR ARCHITECT OF RECORD. |
| FAC 61G1-16.004. |
| PLEASE SEE THIS COMMENT IS FOR ALL |
| TRADES AND FOR ALL SHEETS WHETHER OR NOT |
| COMMENT IS MADE BY OTHER REVIEWER(S). |
| PLEASE KNOW THIS COMMENT DOES NOT APPLY |
| TO KAMM CONSULTING'S TITLE BLOCK. |
| |
| PLEASE SEE ANY OTHER POSSIBLE COMMENTS |
| FROM OTHER TRADES WHICH MAY AFFECT |
| ELECTRICAL PLANS. |
| |
| PLEASE REMOVE ALL OLF/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| |
| ** PLEASE SEE THIS MAY BE CONSIDERED A |
| "THRESHOLD" PROJECT. IF SO, THREE SETS |
| OF PLANS WILL BE REQUIRED. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
| |
| |
| |
| |
| |
2005-09-03 00:00:00 | IN ELEC FOR REVIEW |
| NOTES TO FOLLOW. |