2006-06-02 00:00:00 | ************ UNSAT ************** |
| |
| |
| 1) NOTE: PLEASE SEE RISER IS NOW ON |
| PLANS, HOWEVER IS SERVICE NEW OR |
| EXISTING??? |
| ON ONE SET OF PREVIOUS REVIEWED PLANS IT |
| WAS STATED AS EXISTING AND AIC RATINGS |
| ARE NOT REQUIRED, HOWEVER PREVIOUS PLANS |
| HAVE ALSO SHOWN THE SERVICE AS NEW AND |
| AIC RATINGS WERE REQUESTED. |
| PLEASE INDICATE IF SERVICE IS NEW OR |
| EXISTING? IF NEW PROVIDE AIC RATINGS |
| FOR MAINS ETC. PER 110.9, 215.5 |
| |
| 2) NOTE: PLEASE SEE PLANS STILL DO NOT |
| CONTAIN THE PANEL SCHEDULE FOR THE |
| CABANA SHOWING THE CIRCUITS, OVERCURRENT |
| PROTECTION FOR CIRCUITS AND WIRE SIZES?? |
| THIS WAS SOMETHING WHICH WAS ON PREVIOUS |
| PLANS, HOWEVER IS NOT ON THESE PLANS.?? |
| PLEASE BE SURE THE REQUIRED DEDICATE AND |
| ARC FAULT CIRCUITS ARE SHOWN. |
| PLEASE SEE THE A/C SHEETS CONTAIN PANELS |
| SCHEDULES FOR HOUSE AND CABANA, HOWEVER |
| THESE PANELS SCHEDULES ARE "BLANK"?? |
| 210.12,210.11C3, ETC. |
| |
| 3) NOTE: PLEASE INCLUDE THE OCP FOR THE |
| NEW SUB PANEL FEED. THE RISER MENTIONS |
| NEW 2-POLE, HOWEVER WHAT SIZE IS THIS?? |
| |
| 4) NOTE: PLEASE SEE IF THE SERVICE IS |
| NEW, PLEASE PROVIDE A MIN OF TWO GRND |
| RODS AND CWP AT MAIN HOUSE. IF THE |
| SERVICE IS EXISTING, THEN THIS IS NOT |
| NEEDED. |
| 250.50 |
| |
| 5) NOTE: PLEASE SHOW THE LOCATION AND |
| DISCONNECTING MEANS FOIR THE AHU AND CU. |
| PLEASE SEE THE MECH SHEET SHOWS THE AHU |
| IN CLOSET, HOWEVER THE ELECTRICAL PLANS |
| ONLY INDICATE THE WATER HEATER.?? |
| 440.11, 215.5 |
| |
| 6) NOTE: PLEASE SEE LOCATION OF NEW SUB |
| PANEL IS NOT SHOWN ON PLANS?? |
| |
| |
| 7) NOTE: PLEASE KNOW , IT IS THE |
| RESPONSIBILITY OF THE ENGINEER SIGNING |
| AND SEALING PLANS ONLY TO SIGN AND SEAL |
| PLANS IN WHICH WERE DONE BY SAID |
| ENGINEER OR IS UNDER HIS DIRECT |
| SUPERVISION.FS 471 |
| PLEASE KNOW, IT IS ALSO THE |
| RESPONSIBILTY TO REVIEW AND CHECK PLANS |
| FOR CODE COMPLIANCE BEFORE SIGNING AND |
| SEALING SAID PLANS. |
| THIS IS THE 7TH REVIEW FOR THIS SCOPE OF |
| WORK. PLEASE KNOW IF ALL CORRECTIONS ARE |
| NOT MADE FOR THE FOLLOWING REVIEW, A 4X |
| FEE WILL BE ACCESSED PER FS 553.80(2)(B) |
| AND ALL PLANS RETAINED FOR THIS JOB FROM |
| PREVIOUS REVIEWS AND NEW PLANS WILL BE |
| TURNED OVER TO THE FLORIDA BOARD OF |
| PROFESSIONAL ENGINEERS, AND LEGAL |
| COUNSEL FOR REVIEW. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |