2006-06-02 00:00:00************ UNSAT **************
  
  
 1) NOTE: PLEASE SEE RISER IS NOW ON
 PLANS, HOWEVER IS SERVICE NEW OR
 EXISTING???
 ON ONE SET OF PREVIOUS REVIEWED PLANS IT
 WAS STATED AS EXISTING AND AIC RATINGS
 ARE NOT REQUIRED, HOWEVER PREVIOUS PLANS
 HAVE ALSO SHOWN THE SERVICE AS NEW AND
 AIC RATINGS WERE REQUESTED.
 PLEASE INDICATE IF SERVICE IS NEW OR
 EXISTING? IF NEW PROVIDE AIC RATINGS
 FOR MAINS ETC. PER 110.9, 215.5
  
 2) NOTE: PLEASE SEE PLANS STILL DO NOT
 CONTAIN THE PANEL SCHEDULE FOR THE
 CABANA SHOWING THE CIRCUITS, OVERCURRENT
 PROTECTION FOR CIRCUITS AND WIRE SIZES??
 THIS WAS SOMETHING WHICH WAS ON PREVIOUS
 PLANS, HOWEVER IS NOT ON THESE PLANS.??
 PLEASE BE SURE THE REQUIRED DEDICATE AND
 ARC FAULT CIRCUITS ARE SHOWN.
 PLEASE SEE THE A/C SHEETS CONTAIN PANELS
 SCHEDULES FOR HOUSE AND CABANA, HOWEVER
 THESE PANELS SCHEDULES ARE "BLANK"??
 210.12,210.11C3, ETC.
  
 3) NOTE: PLEASE INCLUDE THE OCP FOR THE
 NEW SUB PANEL FEED. THE RISER MENTIONS
 NEW 2-POLE, HOWEVER WHAT SIZE IS THIS??
  
 4) NOTE: PLEASE SEE IF THE SERVICE IS
 NEW, PLEASE PROVIDE A MIN OF TWO GRND
 RODS AND CWP AT MAIN HOUSE. IF THE
 SERVICE IS EXISTING, THEN THIS IS NOT
 NEEDED.
 250.50
  
 5) NOTE: PLEASE SHOW THE LOCATION AND
 DISCONNECTING MEANS FOIR THE AHU AND CU.
 PLEASE SEE THE MECH SHEET SHOWS THE AHU
 IN CLOSET, HOWEVER THE ELECTRICAL PLANS
 ONLY INDICATE THE WATER HEATER.??
 440.11, 215.5
  
 6) NOTE: PLEASE SEE LOCATION OF NEW SUB
 PANEL IS NOT SHOWN ON PLANS??
  
  
 7) NOTE: PLEASE KNOW , IT IS THE
 RESPONSIBILITY OF THE ENGINEER SIGNING
 AND SEALING PLANS ONLY TO SIGN AND SEAL
 PLANS IN WHICH WERE DONE BY SAID
 ENGINEER OR IS UNDER HIS DIRECT
 SUPERVISION.FS 471
 PLEASE KNOW, IT IS ALSO THE
 RESPONSIBILTY TO REVIEW AND CHECK PLANS
 FOR CODE COMPLIANCE BEFORE SIGNING AND
 SEALING SAID PLANS.
 THIS IS THE 7TH REVIEW FOR THIS SCOPE OF
 WORK. PLEASE KNOW IF ALL CORRECTIONS ARE
 NOT MADE FOR THE FOLLOWING REVIEW, A 4X
 FEE WILL BE ACCESSED PER FS 553.80(2)(B)
 AND ALL PLANS RETAINED FOR THIS JOB FROM
 PREVIOUS REVIEWS AND NEW PLANS WILL BE
 TURNED OVER TO THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS, AND LEGAL
 COUNSEL FOR REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  