Plan Review Notes For Permit 05081294 |
Permit Number |
05081294 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2006-02-01 00:00:00 | **** UNSAT 3RD REVIEW **** | | | | 1)NOTE: PLEASE SEE 220.31B FOR MINIMUM | | LOAD CALCUALTIONS. | | PLEASE SEE CALCUALTIONS AS SHOWN DO NOT | | MEET CODE. | | PLEASESEE DERATING FOR A/C LOADS ARE | | NOT CORRECT. | | PLEASE SEE GEN LT AND RECEPT LOADS ARE | | NOT CORRECT. | | PLEASE SEE LOADS FIGURED INTO EXISTING | | MAIN IS NOT CORRECT. | | ETC. | | ** PLEASE SEE 220.31B. | | | | ** PLEASE SEE IF ALL OTHER COMMENTS ARE | | ADDRESSED FROM ALL OTHER REVIEWER(S), | | PLEASE CALL FOR POSSIBLE OPTIONS. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 |
|