Plan Review Notes
Plan Review Notes For Permit 05081294
Permit Number 05081294
Review Stop E
Sequence Number 2
Notes
Date Text
2005-11-21 00:00:00*** UNSAT ***
  
  
 ** PLEASE SEE ZONING COMMENT. THE
 PROPOSED RESIDENCE IS NOT PERMITTED.
  
  
 1)NOTE: PLEASE SEE PLANS INDICATE
 KITCHEN SM APPLIANCE CIRCUITS, WHICH IS
 ALSO NOT PERMITTED BY ZONING.
  
 2)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND EXISTING PANEL SCHEDULE.
 PLEASE SEE FEEDERS, #3, #4.
 PLEASE SEE MIN PER 310.15B6
  
 3)NOTE: PLEASE SEE MIN LOAD CALCULATIONS
 PER 220.31B.
 PLEASE REVISE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  