Plan Review Notes
Plan Review Notes For Permit 05081294
Permit Number 05081294
Review Stop B
Sequence Number 1
Notes
Date Text
2005-09-23 00:00:00DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) THE INTERNAL PRESSURE COEIFFICIENT IS
 MISSING THE PLUS AND MINUS SIGNS
 INDICATING POSITIVE AND NEGATIVE
 PRESSURES. SEE ASCE 7-98.
  
 4) AN EGRESS DOOR WITH A MINIMUM 32"
 WIDE CLEAR OPENING IS REQUIRED. IF USING
 A DOUBLE DOOR ONE OF THE LEAFS MUST
 COMPLY. SEE 2001 FBC 1003.2.3, 1012.1.7
 AND 1012.1.8.
  
 5) THE BEDROOM WINDOW MUST COMPLY WITH
 THE EMERGENCY EGRESS REQUIREMENTS OF
 1005.4.
  
 6) PROVIDE AN EXTERIOR WALL SECTION ON
 THE PLANS. FBC 104.2
  
 7) 1804.1.3 THE BOTTOM OF THE FOUNDA-
 TION SHALL EXTEND NO LESS THAN 12"
 BELOW FINISH GRADE.
  
 8) SPECIFY A 1.5 INCH RECESS IN THE
 CONCRETE FLOOR SURFACE WHERE THE
 EXTERIOR WALL MASONRY UNITS BEAR. CITY
 AMENDMENTS TO FBC 2111.1.9.
  
 9) CITY AMENDMENTS TO FBC 1804.1.7
 REQUIRE THE FLOOR ELEVATION AT THE
 PERIMETER OF A MONOLITHIC FOUNDATION AT
 HABITABLE AREAS TO BE A MINIMUM OF 4
 INCHES ABOVE THE EXTERIOR FINISH GRADE.
  
 10)FL BLD CODE 2309.6 ATTIC ACCESS,
 PROVIDE ATTIC ACCESS 20"X36" MINIMUM.
  
 11) SPECIFY ATTIC VENTILATION AS
 REQUIRED BY FBC 2309.7.
  
 12) SPECIFY THE LOCATION OF THE 40 GAL.
 ELECTRIC WATER HEATER. FBC 104.2
  
 13) PROVIDE A SITE PLAN SPECIFING THE
 ASSUMED PROPERTY LINE BETWEEN THE THE
 TWO STRUCTURES LOCATED ON THE SAME LOT.
 PROVIDE CALCULATIONS OF THE PERCENT OF
 WALL AREA ALLOWED AS OPENINGS BY FBC
 TABLE 600 FOR THE EXISTING AND THE NEW
 STRUCTURES. FBC 504 AND TABLE 600.
  
 14) SPECIFY THE CONNECTION TYPE AND THE
 ANCHOR TYPE THAT WILL BE USED FOR THE
 STORM PANELS. SEE SHEET 4 OF THE PRODUCT
 APPROVAL. THE STORM PANEL INSTALLATION
 SCHEDULE LISTS WING NUTS AS THE ANCHOR
 TYPE. THIS IS NOT ONE OF THE ANCHORS
 LISTED ON THE PRODUCT APPROVAL. THE
 SCHEDULE ALSO INDICATES THAT THE PANELS
 ARE BOLTED. THIS REFERS TO PANELS WITH
 LONG SPANS THAT ARE REQUIRED TO BE
 BOLTED TOGETHER IN THE MIDDLE OF THE
 SPAN. THIS IS NOT NECESSARY FOR YOUR
 PROJECT.
  
 15) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SUBMIT A
 COVER SHEET FOR THE ROOF SHINGLES.
  
 16) THE FL COVER SHEET FOR THE STANLEY
 DOOR SYSTEM DOES NOT MATCH THE MIAMI
 DADE NOA.
  
 17) THE MIAMI DADE NOA FOR THE SINGLE
 HUNG WINDOWS IS NOT THE ONE LISTED ON
 THE STATE WEBSITE FOR THE FL #
 SUBMITTED. THE CORRECT ONE IS NOA #
 02-1203.02.
  
 18) THE DRAWINGS ATTACHED TO THE STANLEY
 DOOR NOA DO NOT BELONG WITH THE NOA.
 THEY HAVE DIFFERENT APPROVAL NUMBERS.
  
 19) SUBMIT PRODUCT APPROVALS FOR THE
 SINGLE INSWING EXTERIOR DOOR AND THE
 DOUBLE OUTSWING EXTERIOR DOOR.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  
  