Date |
Text |
2005-09-23 00:00:00 | DENIED |
| |
| 1)A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2)IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 3) THE INTERNAL PRESSURE COEIFFICIENT IS |
| MISSING THE PLUS AND MINUS SIGNS |
| INDICATING POSITIVE AND NEGATIVE |
| PRESSURES. SEE ASCE 7-98. |
| |
| 4) AN EGRESS DOOR WITH A MINIMUM 32" |
| WIDE CLEAR OPENING IS REQUIRED. IF USING |
| A DOUBLE DOOR ONE OF THE LEAFS MUST |
| COMPLY. SEE 2001 FBC 1003.2.3, 1012.1.7 |
| AND 1012.1.8. |
| |
| 5) THE BEDROOM WINDOW MUST COMPLY WITH |
| THE EMERGENCY EGRESS REQUIREMENTS OF |
| 1005.4. |
| |
| 6) PROVIDE AN EXTERIOR WALL SECTION ON |
| THE PLANS. FBC 104.2 |
| |
| 7) 1804.1.3 THE BOTTOM OF THE FOUNDA- |
| TION SHALL EXTEND NO LESS THAN 12" |
| BELOW FINISH GRADE. |
| |
| 8) SPECIFY A 1.5 INCH RECESS IN THE |
| CONCRETE FLOOR SURFACE WHERE THE |
| EXTERIOR WALL MASONRY UNITS BEAR. CITY |
| AMENDMENTS TO FBC 2111.1.9. |
| |
| 9) CITY AMENDMENTS TO FBC 1804.1.7 |
| REQUIRE THE FLOOR ELEVATION AT THE |
| PERIMETER OF A MONOLITHIC FOUNDATION AT |
| HABITABLE AREAS TO BE A MINIMUM OF 4 |
| INCHES ABOVE THE EXTERIOR FINISH GRADE. |
| |
| 10)FL BLD CODE 2309.6 ATTIC ACCESS, |
| PROVIDE ATTIC ACCESS 20"X36" MINIMUM. |
| |
| 11) SPECIFY ATTIC VENTILATION AS |
| REQUIRED BY FBC 2309.7. |
| |
| 12) SPECIFY THE LOCATION OF THE 40 GAL. |
| ELECTRIC WATER HEATER. FBC 104.2 |
| |
| 13) PROVIDE A SITE PLAN SPECIFING THE |
| ASSUMED PROPERTY LINE BETWEEN THE THE |
| TWO STRUCTURES LOCATED ON THE SAME LOT. |
| PROVIDE CALCULATIONS OF THE PERCENT OF |
| WALL AREA ALLOWED AS OPENINGS BY FBC |
| TABLE 600 FOR THE EXISTING AND THE NEW |
| STRUCTURES. FBC 504 AND TABLE 600. |
| |
| 14) SPECIFY THE CONNECTION TYPE AND THE |
| ANCHOR TYPE THAT WILL BE USED FOR THE |
| STORM PANELS. SEE SHEET 4 OF THE PRODUCT |
| APPROVAL. THE STORM PANEL INSTALLATION |
| SCHEDULE LISTS WING NUTS AS THE ANCHOR |
| TYPE. THIS IS NOT ONE OF THE ANCHORS |
| LISTED ON THE PRODUCT APPROVAL. THE |
| SCHEDULE ALSO INDICATES THAT THE PANELS |
| ARE BOLTED. THIS REFERS TO PANELS WITH |
| LONG SPANS THAT ARE REQUIRED TO BE |
| BOLTED TOGETHER IN THE MIDDLE OF THE |
| SPAN. THIS IS NOT NECESSARY FOR YOUR |
| PROJECT. |
| |
| 15) PRODUCT APPROVALS SUBMITTED |
| WITH PERMIT APPLICATION AFTER OCTOBER 1, |
| 2003 ARE REQUIRED TO COMPLY WITH THE |
| FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| INFORMATION PLEASE SEE THE STATE WEBSITE |
| AT WWW.FLORIDABUILDING.ORG. PRODUCTS |
| WITH STATEWIDE APPROVAL ARE REQUIRED TO |
| BE SUBMITTED WITH A COVER SHEET THAT |
| LISTS THE PRODUCT IDENTITY NUMBER FROM |
| THE STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SUBMIT A |
| COVER SHEET FOR THE ROOF SHINGLES. |
| |
| 16) THE FL COVER SHEET FOR THE STANLEY |
| DOOR SYSTEM DOES NOT MATCH THE MIAMI |
| DADE NOA. |
| |
| 17) THE MIAMI DADE NOA FOR THE SINGLE |
| HUNG WINDOWS IS NOT THE ONE LISTED ON |
| THE STATE WEBSITE FOR THE FL # |
| SUBMITTED. THE CORRECT ONE IS NOA # |
| 02-1203.02. |
| |
| 18) THE DRAWINGS ATTACHED TO THE STANLEY |
| DOOR NOA DO NOT BELONG WITH THE NOA. |
| THEY HAVE DIFFERENT APPROVAL NUMBERS. |
| |
| 19) SUBMIT PRODUCT APPROVALS FOR THE |
| SINGLE INSWING EXTERIOR DOOR AND THE |
| DOUBLE OUTSWING EXTERIOR DOOR. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| |
| |
| |
| |
| |
| |