Plan Review Notes
Plan Review Notes For Permit 05081277
Permit Number 05081277
Review Stop P
Sequence Number 1
Notes
Date Text
2005-09-10 00:00:00DENIED;
 1.AN APPLICATION FOR COM. REMODEL, FOR
 THE REMODELING OF THE BATHROOMS SHALL BE
 SUBMITED BY AN APPROIATE CONTRACTOR TO
 DEMO THE EXISTING FLOOR PLAN AND
 CONSTRUCT NEW WALLS ETC. SECTION 104.1.
 2.SUBMIT A DETAIL FOR THE BATHROOMS
 SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.19, AND ALL SUBSECTIONS.
 3.A DRINKING FOUNTAIN IS REQUIRED IN
 EACH SPACE TABLE 403.1.
 4.SUBMIT A WATER RISER DIAGRAM SHOWING
 ALL PIPE SIZES,VAVES, WATER HAMMER
 ARRESTORS, WHERE REQUIRED BY 604.9 AND
 POINT OF CONNECTION.
 5. A RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE BUILDING. PLEASE
 INDICATE IF THERE IS AN EXISTING RPZ ON
 WATER SERVICE. SEC.608.12.2.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695