Plan Review Notes For Permit 05081277 |
Permit Number |
05081277 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-09-10 00:00:00 | DENIED; | | 1.AN APPLICATION FOR COM. REMODEL, FOR | | THE REMODELING OF THE BATHROOMS SHALL BE | | SUBMITED BY AN APPROIATE CONTRACTOR TO | | DEMO THE EXISTING FLOOR PLAN AND | | CONSTRUCT NEW WALLS ETC. SECTION 104.1. | | 2.SUBMIT A DETAIL FOR THE BATHROOMS | | SHOWING COMPLIANCE WITH SECTIONS | | 11-4.16, 11-4.19, AND ALL SUBSECTIONS. | | 3.A DRINKING FOUNTAIN IS REQUIRED IN | | EACH SPACE TABLE 403.1. | | 4.SUBMIT A WATER RISER DIAGRAM SHOWING | | ALL PIPE SIZES,VAVES, WATER HAMMER | | ARRESTORS, WHERE REQUIRED BY 604.9 AND | | POINT OF CONNECTION. | | 5. A RPZ BACKFLOW IS REQUIRED ON THE | | WATER SERVICE TO THE BUILDING. PLEASE | | INDICATE IF THERE IS AN EXISTING RPZ ON | | WATER SERVICE. SEC.608.12.2. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|