Plan Review Notes
Plan Review Notes For Permit 05081218
Permit Number 05081218
Review Stop E
Sequence Number 2
Notes
Date Text
2005-09-10 00:00:00******** UNSAT **********
  
 1)NOTE: PLEASE SEE RISER DIAGRAM NEEDS
 TO BE COMPLETELYREVISED TO MEET ZONING
 GREEN CARD.
 THIS MAY ONLY BE A MAIN HOUSE W/ A
 GARAGE APT. THIS WOULD ONLY BE ALLOWED
 TO HAVE TWO METERS. ONE FOR EACH AND NO
 HOUSE PANEL.
  
 PLEASE SEE ANY LEGAL CONVERSIONS, MUST
 BE RESERCHED TO ALLOW FOR ANY MORE THAN
 THE TWO ON GREEN CARDS AS INDICATED.
 ALL RESERCH REQUESTS MUST GO THROUGH
 APRIL PICCIRILLO, 805-6658
  
  
  
 2)NOTE: PLEASE SEE RISER SUBMITTED IF
 APPROVED BY ZONING HAS CORRECTION
 NEEDED.
 PLEASE SEE ALL FEEDS FOR EACH COME FROM
 LEFT SIDE OF METER CENTER.
 PLEASE LABEL ALL MAINS ON METER CENTER
 FOR EACH HOUSE/APT.
 PLEASE SEE TWO APT "B"'S ARE SHOWN.
 PLEASE SEE MAIN HOUSE IS ALSO INDICATED
 AS APT "B".??
  
  
 3)NOTE: PLEASE SEE ALL CONTINUOUS LOADS
 ARE TO BE SHOWN AT 125%.
 HEAT PUMP, POOL PUMP ETC.
 215.3,230.42,680.9
  
 4)NOTE: PLEASE SEE MIN BRANCH CIRCUIT
 CONDUCTOR AMPACITY FOR TANKLESS WATER
 HEATER UNITS MUST BE 125%.
 422.13
 PLEASE ALSO SEE 422.11F1
  
 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 6)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52
  
 7 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 2002 NEC 210.12
  
 8)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 9) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
 MUST BE 20A AND #12.
  
 10) NOTE: PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52E
 ALSO 210.8 FOR GFI.
  
 11)NOTE: PLEASE SEE MISSING RECEPT
 REQ'D FOR A/C EQUIPMENT. 210.63
  
 12)NOTE: PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5
 SEE REDLINED PLANS FOR MISSING.
  
 13)NOTE: PLEASE SEE SEE SPA TUB SHOWN,
 HOWEVER NO ELECTRICAL GFI ETC??
 680.71
 IS THIS AN ELECTRICAL JACUZZI TUB?
  
 14)NOTE: PLEASE SEE FBC CHAPTER 34 WITH
 RENOVATIONS TO EXSITNG DWELLINGS.
 PLEASE SEE ALL MUST BE BROUGHT UP TO
 CODE, INCLUDING 2NF FLR AT DEATCHED
 BLDG.
 PLEASE PROVIDE COMPLETE LAYOUT FOR
 EITHER EXSITNG TO MEET CODE OR NEW TO BE
 DONE ON SCOPE OF WORK.
  
 15)NOTE: PLEASE SEE ADMINISTRATIVE
 AMENDMENTS, 104.6.5, WHICH REQUIRES ALL
 LABOR AND MATERIALS TO BE INCLUDED IN
 VALUE OF PERMIT APPLICATION.
 PLEASE SEE VALUE FOR SERVICE CHANGE
 PERMIT WILL ALSO BE REQUIRED TO BE
 UPGRADED.
 IFVALUES ARE NOT AJUSTED, A VALUATION
 WILL BE GIVEN BASED ON TABLE IN "MARSHAL
 SWIFT " GUIDES ADOPTED UNDER FBC.
  
 ** PLEASE SEE MANY OF THE ABOVE COMMENTS
 DEPEND ON ZONING AND APPROVAL FOR MORE
 THAN TWO METERS AND DETACHED BLDG
 POSSIBLY REMAINING GARAGE WITH APT
 ABOVE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved