Plan Review Notes For Permit 05081156 |
Permit Number |
05081156 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-10-06 00:00:00 | *** PROVISO *** | | 1) GENERATOR EXHUST MUST BE TEN FEET | | AWAY FROM ANY BUILDING OPENINGS | | (WINDOWS, DOORS, ROOF & EAVE VENTS), AND | | TEN FEET AWAY FROM ADJECENT BUILDING | | OPENINGS. PER 2001 FBC/M 804.3.3 . | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | TOM GORDON 805-6729 OR PATTY KRAUSS | | 805-6719. |
|