2005-10-05 00:00:00*** REDLINED PLANS.
  
 CONDUCTORS FROM ATS TO MCB PANELS TO BE
 MAIN OF 1/0'S, #3' SHOWN.
 NO EQUIPMENT GROUNDING CONDUCTOR FROM
 METER TO ATS/ FIRST MEANS OF DISCONNECT.
 250.6,250.24