Plan Review Notes For Permit 05081156 |
Permit Number |
05081156 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-09-08 00:00:00 | *** DENIED *** | | 1) PLANS MUST INICATE ANY BUILDING | | OPENINGS (WINDOWS, DOORS, ROOF/EAVE | | VENTS.GENERATOR EXHAUST MUST BE TEN | | FEET AWAY FROM ANY BUILDING OPENINGS, | | AND TEN FEET AWAY FROM ADJACENT | | BUILDING OPENINGS. 2001 FBC/M 804.3.3 | | 2) NATURAL GAS PIPING WILL REQUIRE A | | GAS PERMIT APPLICATION BY A LICENSE | | PLUMBING CONTRACTOR. | | 3) PLEASE SEE ELECTRICAL REVIEW NOTES | | #1 AND "#7" . | | IF YOU HAVE ANY QUESEIONS PLEASE CALL | | TOM GORDON 805-6729 OR PATTY KRAUSS | | 805-6719 . |
|