2005-09-01 00:00:00 | ********** UNSAT ************ |
| |
| |
| |
| 1)NOTE: PLEASE SUBMIT TWO COPIES OF |
| MANUFACTURES SPECS/CUT SHEETS FOR |
| GENERATOR AND ATS. |
| |
| |
| 2)NOTE: PLEASE SEE CONDUCTORS FROM METER |
| TO ATS. PLEASE SEE THE # OF CONDUCTORS, |
| AS IT APPEARS AN "EQUIPMENT GROUNDING |
| CONDUCTOR" IS BEING INSTALLED. PLEASE |
| SEE 250.6, AN EQP GRNDING CONDUCTOR IS |
| ONLY INSTALLED AFTER THE FIRST MEANS OF |
| DISCONNECT. PLEASE INDICATE OF THE ATS |
| WILL BE THE FIRST MEANS OF DISCONNECT AS |
| IT IS SHOWN THIS WAY ON RISER. PLEASE |
| SEE 230.76,230.79, THE MEANS OF |
| DISCONNECT SAHHL MANUAL AND LOCATED ON |
| THE OUTSIDE OF THE EQUIPMENT. |
| |
| 3)NOTE: PLEASE SEE 225.31 FOR MISSING |
| MEANS OF DISCONNECT. PLEASE SEE 225.34 |
| FOR GROUPING OF THIS MEANS OF DISCONNECT |
| WITH EXISTING MAIN(S). |
| PLEASE SEE 225.36, THIS DISCONNECTING |
| MEANS SHALL BE LISED AS "SERVICE |
| EQUIPMENT". SPECS DO INDICATE THIS FOR |
| SERVICE EQUIPMENT RATED. |
| |
| 5)NOTE: PLEASE SEE 225.35FOR LOADS |
| /CALCULATION WHICH IS BEING RE-FED. |
| PLEASE SEE LOADS SHALL BE INCREASED AT |
| 125%. |
| 702.5 |
| |
| 6)NOTE: PLEASE SEE SIZE OF CONDUCTORS |
| INDICATE FOR THE TWO 150A PANELS. PLEASE |
| SEE #3 IS RATED FOR 110A'S,310.15B6 |
| PLEASE SEE SHEET INDICATES SERVICE AT |
| 300A'S. |
| |
| 7)NOTE: PLEASE BE SURE ALL |
| PLANS/DRAWINGS CONTAIN THE PRINTED ANME |
| AND SIGNATURE OF THE PERSON RESPONSIBLE |
| FOR PLANS/ DESIGN. |
| FBC 104.2.1, ADMINISTRATIVE CODE |
| CITY-WIDE AMENDMENTS. |
| |
| 7)NOTE: PLEASE SEE THE VALUATION FOR |
| PERMIT APPLICATION SHALL INCLUDE ALL |
| LABOR AND MATERIALS EVEN IF MATERIALS |
| (GEN) IS OWNER SUPPPLIED. |
| 104.6.5 |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |