Date |
Text |
2005-09-01 00:00:00 | ********* UNSAT ********* |
| |
| 1)NOTE: PLEASE SEE COMMENTS FROM OTHER |
| REVIEWER(S). BLDG FOR SLAB DETAIL |
| SUBMITTED. |
| |
| 2)NOTE: PLEASE SEE SITE PLAN SUBMITTED |
| SHOWS GENERATOR RIGHT NEXT TO HOUSE?? |
| PLEASE SHOW SET BACK AND DIMENTIONS FROM |
| DWELLING STRUCTURE. |
| PLEASE SEE MECH NOTES, MUST BE 10' FROM |
| ANY OPENINGS TO HOUSE,ATTIC VENTILATION, |
| DOORS AND WINDOWS. |
| |
| 3)NOTE: PLEASE CORRELATE RISER DIAGRAM |
| WITH PANEL SCHEDULES SUBMITTED. |
| PLEASE SEE RISER SHOWS 2 PANELS, BOTH |
| 200A WITH 2/0'S. PLEASE SEE PANEL "A" |
| SHOWN AS 150A W/ #1 AS FEEDERS?? |
| PLEASE SEE PANEL "C" IS NOT SHOWN ON |
| RISER AND SEE PANEL "B" SHOWS 100A OCP |
| ON #6 AWG. PLEASE SEE 240.4,310.16 ETC. |
| |
| 4)NOTE: PLEASE SEE EQUIPMENT GROUNDING |
| CONDUCTOR SHOWN FROM METER TO FIRST |
| MEANS OF DISCONNECT. |
| PLEASE SEE 250.6, |
| |
| 5)NOTE: PLEASE SEE EXISTING SERVICE IS |
| SHOWN AS 400A, YET NEW MAIN AND ATS |
| SHOWN BRINGS SERVICE DOWN TO 300A'S?? |
| PLEASE SUBMIT MORE INFORMATION ON NEW |
| MAIN SHOWN ON RISER. OCP? ETC |
| AIC RATINGS FOR ALL EQUIPMENT BEING |
| INSTALLED, MAIN, ATS ETC |
| 702.6,110.9 ETC. |
| |
| 6)NOTE: PLEASE SUBMIT SPEC ON ATS, |
| SHEETS SUBMITTED DOES NOT PROVIDE |
| INFORMATION FOR RATING PER 225.36, |
| 230.70 |
| MUST INDICATE BEING RATED AS SERVICE |
| EQUIPMENT. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |