Plan Review Notes
Plan Review Notes For Permit 05081151
Permit Number 05081151
Review Stop E
Sequence Number 1
Notes
Date Text
2005-09-01 00:00:00********* UNSAT *********
  
 1)NOTE: PLEASE SEE COMMENTS FROM OTHER
 REVIEWER(S). BLDG FOR SLAB DETAIL
 SUBMITTED.
  
 2)NOTE: PLEASE SEE SITE PLAN SUBMITTED
 SHOWS GENERATOR RIGHT NEXT TO HOUSE??
 PLEASE SHOW SET BACK AND DIMENTIONS FROM
 DWELLING STRUCTURE.
 PLEASE SEE MECH NOTES, MUST BE 10' FROM
 ANY OPENINGS TO HOUSE,ATTIC VENTILATION,
 DOORS AND WINDOWS.
  
 3)NOTE: PLEASE CORRELATE RISER DIAGRAM
 WITH PANEL SCHEDULES SUBMITTED.
 PLEASE SEE RISER SHOWS 2 PANELS, BOTH
 200A WITH 2/0'S. PLEASE SEE PANEL "A"
 SHOWN AS 150A W/ #1 AS FEEDERS??
 PLEASE SEE PANEL "C" IS NOT SHOWN ON
 RISER AND SEE PANEL "B" SHOWS 100A OCP
 ON #6 AWG. PLEASE SEE 240.4,310.16 ETC.
  
 4)NOTE: PLEASE SEE EQUIPMENT GROUNDING
 CONDUCTOR SHOWN FROM METER TO FIRST
 MEANS OF DISCONNECT.
 PLEASE SEE 250.6,
  
 5)NOTE: PLEASE SEE EXISTING SERVICE IS
 SHOWN AS 400A, YET NEW MAIN AND ATS
 SHOWN BRINGS SERVICE DOWN TO 300A'S??
 PLEASE SUBMIT MORE INFORMATION ON NEW
 MAIN SHOWN ON RISER. OCP? ETC
 AIC RATINGS FOR ALL EQUIPMENT BEING
 INSTALLED, MAIN, ATS ETC
 702.6,110.9 ETC.
  
 6)NOTE: PLEASE SUBMIT SPEC ON ATS,
 SHEETS SUBMITTED DOES NOT PROVIDE
 INFORMATION FOR RATING PER 225.36,
 230.70
 MUST INDICATE BEING RATED AS SERVICE
 EQUIPMENT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  