Plan Review Notes
Plan Review Notes For Permit 05081143
Permit Number 05081143
Review Stop B
Sequence Number 2
Notes
Date Text
2005-09-16 00:00:001) THE DRAWINGS FOR THE FOOTING DETAIL
 NEEDS TO BE SIGNED/DATED AND SEAL BY THE
 ENGINEER OF RECORD.
 F.A.C. 61G15-23.002.
  
 2) THE DRAWINGS FOR THE FOOTING DETAIL
 HAS BEEN COPY AND PASTE ON THE NEW
 SHEETS SUBMITTED.HOWEVER, THESE DRAWINGS
 NEEDS THE PRINTED NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DRAWINGS.
  
 3) THE FOOTING DETAIL STATES A MINIMUM
 PSI OF 2500. THE CONCRETE DETAIL ON THE
 ENGINEERED DRAWINGS STATES 3000 PSI.
 PLEASE CLARIFY THESE TWO DETAILS.
  
 BUILDING PLAN REVIEW
 MYRON JACOBS
 TEL: (561)805-6726
 FAX: (561)659-8026
  