Plan Review Notes For Permit 05081136 |
Permit Number |
05081136 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-08-17 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 05081136 | | ADD: 234 VALENCIA RD | | CONT CARLO MERCURIO | | TEL: (561)329-8167 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 1ST REVIEW | | ACTION: DENIED | | ) THIS ROOF IS MISSING OR NOT IN | | COMPLIANCE WITH THE FOLLOW ITEMS: | | | | _X__ CONTRACTOR DID NOT PROVIDE THE MEAN | | | | ROOF HEIGHT. | | | | _X__ CONTRACTOR DID NOT INDICATE THE | | ROOF | | | | PITCH. | | | | _X__ CONTRACTOR FAILED TO INDICATE WHICH | | SYSTEM TO BE USED. | | | | _X__ THE SYSTEM PROVIDED HAS A LOW | | PRESSURE FOR ZONE _3__ . | | | | _X__ THE SYSTEM PROVIDED STATES | | LIMITATION# 7, SHOULD THE FASTENER | | RESISTANCE BE LESS THAN THAT | | REQUIRED, AS DETERMINED BY THE | | BUILDING OFFICIAL, A REVISED | | FASTENER SPACING, PREPARED , SIGNED | | AND SEALED BY A FLORIDA REGISTERED | | PROFESSIONAL ENGINEER, REGISTERED | | ARCHITECT OR REGISTERED ROOF | | CONSULTANT MAY BE SUBMITTED. | | | | ___THE SYSTEM PROVIDED INDICATES | | LIMITATION# 9, NO ENHANCED | | FASTENING ALLOWED. | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|