Plan Review Notes For Permit 05081135 |
Permit Number |
05081135 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-10-05 00:00:00 | PLAN DENIED | | 1) HEAT PUMPS THAT CAN PRODUCE OVER 2000 | | CFM.MUST HAVE FAN SHUTDOWN.SECTION | | 606.2.1 FBC(M). | | 2) PLEASE REFER TO SECTION 307.2.3 | | AUXILIARY DRAIN PANS. | | 3) PLEASE PROVIDE MORE INFORMATION ON | | SMOKE EVACUATION. | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|