Plan Review Notes
Plan Review Notes For Permit 05081135
Permit Number 05081135
Review Stop E
Sequence Number 1
Notes
Date Text
2005-09-01 00:00:00REDLINEDMISSING EQUIPMENT GROUNDING
 CONDUCTORS, 250.110,250.122
  
 REDLINED 210.8B3 FOR KITCHEN RECEPTS IN
 OTHER THAN DWELLING UNITS.