Plan Review Notes For Permit 05081072 |
Permit Number |
05081072 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-09-19 00:00:00 | BUILDING REVIEW CHECKLIST: | | 1- NEED RECORDED NOTICE OF COMMENCEMENT. | | | | 2- DRAWING IN SCREEN ENCLOSURE | | BEAM-COLUMN CALCULATOR DOESN'T MATCH | | LAYOUT SHOWN ON SHEET 1 OF 1. SEE | | DIMENSIONS AND SHAPE OF SCREEN | | ENCLOSURE. | | | | 3- REVISE LOADS SHOWN ON CALCULATOR | | SHEET. DESIGN LOAD TO BE 10PSF MIN.AS | | REQUIRED BY SEC. 2002.4 FBC 2001. | | | | 4- MISSING SHEET 2 OF 2 OF MASTER PLANS. | | NEED SPAN TABLES TO VERIFY COLUMN AND | | BEAM SPAN. SEC. 104.2.1.2 CITY | | AMENDMENTS TO FBC 2001. | | | | 5- SHEET 1 OF 2 OF MASTER PLAN SAYS THAT | | "MAX ROOF SPAN=38'-0". CLARIFY AS | | REQUIRED. SEE DIMENSIONS ON PROPOSED | | LAYOUT. | | | | 6- PROVIDE DETAILS AND SPECIFICATIONS | | FOR FOOTING TO SUPPORT THE SCREEN | | ENCLOSURE. | | | | 7- PERMIT APPLICATION SAYS FOOTER BY | | OTHERS. WHO'S DOING THE FOOTING. IS IT | | GOING TO BE SEPARATE PERMIT? | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ AT (561)805-6712. |
|