Plan Review Notes
Plan Review Notes For Permit 05081072
Permit Number 05081072
Review Stop B
Sequence Number 1
Notes
Date Text
2005-09-19 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- DRAWING IN SCREEN ENCLOSURE
 BEAM-COLUMN CALCULATOR DOESN'T MATCH
 LAYOUT SHOWN ON SHEET 1 OF 1. SEE
 DIMENSIONS AND SHAPE OF SCREEN
 ENCLOSURE.
  
 3- REVISE LOADS SHOWN ON CALCULATOR
 SHEET. DESIGN LOAD TO BE 10PSF MIN.AS
 REQUIRED BY SEC. 2002.4 FBC 2001.
  
 4- MISSING SHEET 2 OF 2 OF MASTER PLANS.
 NEED SPAN TABLES TO VERIFY COLUMN AND
 BEAM SPAN. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 5- SHEET 1 OF 2 OF MASTER PLAN SAYS THAT
 "MAX ROOF SPAN=38'-0". CLARIFY AS
 REQUIRED. SEE DIMENSIONS ON PROPOSED
 LAYOUT.
  
 6- PROVIDE DETAILS AND SPECIFICATIONS
 FOR FOOTING TO SUPPORT THE SCREEN
 ENCLOSURE.
  
 7- PERMIT APPLICATION SAYS FOOTER BY
 OTHERS. WHO'S DOING THE FOOTING. IS IT
 GOING TO BE SEPARATE PERMIT?
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.