2006-08-23 00:00:00***PROVISO***
  
 SITE AMENITIES
  
 1) ANY UNDERGROUND PIPING INSTALLATION
 SHALL BE TESTED, INSPECTED AND APPROVED
 BY THE BUREAU OF FIRE PREVENTION. ALL
 PIPING JOINTS TO REMAIN UNCOVERED AND
 VISIBLE FOR HYDROSTATIC TESTING.
  
 2) NEW FIRE HYDRANTS TO BE OPERATIONAL
 PRIOR TO, DURING AND AFTER
 CONSTRUCTRION.
  
 3) EMERGENCY VEHICLE ACCESS SHALL COMPLY
 WITH NFPA 1, 2003 EDITION CHAPTER 18.
  
 4) WILL THE GUARDHOUSE BE STAFFED AND IF
 SO, PLEASE INDICATE THE HOURS.
  
 5) PLEASE CLEARLY SHOW LOCATIONS OF FIRE
 HYDRANTS, NEW AND EXISTING AND
 ILLUSTRATE DISTANCES.
  
  