Plan Review Notes
Plan Review Notes For Permit 05081014
Permit Number 05081014
Review Stop P
Sequence Number 2
Notes
Date Text
2006-06-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT A001 INDEX SHEET. ALL SHEETS ON
 INDEX SHEET NOT SUBMITTED. PLEASE SUBMIT
 ALL SHEETS. PLANS NOT COMPLETE. SECTION
 104.2.1.
 *** RESPONSE NOTED, BUT SHTS P001, AND
 P401 WERE SUBMITTED AND NOT ON THE INDEX
 ON SHT A001. PLEASE CORRELATE INDEX AND
 SHEETS SUBMITTED. SECTION 104.2.1.
  
 2. SHTS I-1 & I-2 INFORMATION REQUIRED
 ON IMPRESSION SEAL OF LANDSCAPE
 ARCHITECT IS NOT IMPRESSED ON THE PLANS.
 PLEASE RESEAL SHEETS. FAC 61G1-16.002(1)
 AND FS 481.321.
 *** RESPONSE NOTED, BUT THE INFORMATION
 REQUIRED TO BE IMPRESSED ON EACH SHEET
 IS NOT SHOWN. SEE ALL L-SHEETS AND
 I-SHEET. RESEAL TO SHOW INFORMATION.
  
 3. SHT A101 URINAL REQUIRED IN THE MENS
 TOILET ROOM FOR THE SWIMMING POOL PER
 TABLE 424.1.6.1.
 *** RESPONSE NOTED, BUT FLOOR PLAN SHEET
 SHALL BE RESUBMITTED WITH CHANGE ON THE
 SIGNED, SEALED, DATED SHEET.
 SUPPLEMENTAL SHEETS NOT APPROVED.
 SECTION 104.2.1.3.
  
 4. SHT A101 TOILET ROOMS SHALL COMPLY
 WITH SECTIONS 11-4.16, 11-4.18, 11-4.19,
 AND 11-4.22 AND ALL SUBSECTIONS. PLEASE
 PROVIDE A DETAIL SHOWING ALL
 REQUIREMENTS.
 *** RESPONSE NOTED, BUT ALL ELEVATIONS
 SHALL BE SHOWN FOR THE TOILET ROOMS, ON
 THE FULL SIGNED, SEALED, DATED SHEETS.
 SUPPLEMENTAL SHEETS NOT APPROVED. ALSO
 SHOW THE FOLLOWING:
 A. 11-4.18.4 FLUSH CONTROLS
 B. 11-4.19.5 FAUCETS
 5. SHT A102 TOILET ROOM FOR GUARD HOUSE
 TO COMPLY WITH SECTIONS 11-4.16,
 11-4.19, AND 11-4.22 WITH ALL
 SUBSECTIONS. PLEASE PROVIDE A DETAIL
 SHOWING ALL REQUIREMENTS.
 *** RESPONSE NOTED, BUT SUPPLEMENTAL
 DRAWINGS ARE NOT APPROVED. CHANGES SHALL
 BE SUBMITTED ON THE SIGNED, SEALED,
 DATED SHEETS.
  
 7. PLUMBING PLANS FOR SWIMMING POOL
 TOILET ROOMS WERE NOT SUBMITTED. PLEASE
 SUBMIT THE PLUMBING PLANS ALONG WITH THE
 SANT. AND WATER RISER DIAGRAMS. SECTIONS
 104.2.1 & 104.3.1.1.
 ***RESPONSE NOTED, BUT PLANS SHALL BE
 SUBMITTED UNDER CORRECT PERMIT NUMBER.
 (BLDG 4).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 8056731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved