2006-06-10 00:00:00 | ***** UNSAT2ND REVIEW ****** |
| |
| ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| REVIEW AND SOME NEW NOTES DUE TO THE |
| PLANS ETC SUBMITTED. |
| |
| 1)NOTE:NOTE #1 NO, PLEASE SEE THIS |
| NOTE STILL APPLIES. PLEASE SEE A NEW |
| SHEET WAS ADDED FOR THE BUILDING AND |
| UNIT LAYOUTS WHICH CONTAIN COMMENTS |
| UNDER OTHER REVISIONS WHICH WERE |
| SUBMITTED. |
| PLEASE SEE THE REVISED RISER WHICH WAS |
| SUBMITTED TO ADDRESS THE PANEL "G-1" IN |
| QUESTION HAS COMMENTS AS IT WAS REVISED |
| FOR OTHER ITEMS. SEE NEW NOTES BELOW. |
| |
| ** PREVIOUS REVIEW ** |
| PLEASE SEE PLANS SUBMITTED SEEM |
| TO CONTAIN SHEETS FROM REVIEW FOR BLDG |
| PERMITTED SETS. |
| PLEASE CLARIFY PLANS FOR "SITE" SHOULD |
| CONTAIN SHEETS PERTAINING TO SITE ONLY. |
| SEE RISER DIAGRAM SUBMITTED DOES NOT |
| INCLUDE PANEL "G1". G-1 PANEL SCHEDULE |
| SUBMITTED. |
| |
| 2)NOTE: NOTE #2 NO. THESE WERE NOT |
| SUBMITTED. |
| |
| ** PREVIOUS NOTE ** |
| PLEASE SUBMIT ALL MANUFACTURE |
| SPEC/CUT SHEETS FOR GATE MOTORS AND |
| CONTROLLER. PLEASE SEE ANY FIRE REVIEW |
| COMMENTS FOR "FAIL SAFE" OPERATION IN |
| THE EVENT OF POWER FAILURE. |
| NOTE WAS SHOWN ON "A" SHEET WHICH |
| MENTIONED GATE CAN BE MANUAL. |
| |
| NEW NOTES |
| ************************** |
| |
| 3) NOTE: PLEASE KNOW, ALL OLD/VOIDED |
| SHEETS SHALL BE COMPLETELY REMOVED FROM |
| SETS AND ONLY NEW REVISED SHEET SHOULD |
| BE INSERTED INTO COMPLETE SETS FOR |
| REVIEW AND STAMPING. |
| PLEASE KNOW, ONLY ONE COPY OF ANY |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| ACCOMPANYING THE THREE NEW COMPLETED |
| SETS. |
| ** PLEASE BE SURE THESE SETS ARE |
| SUBMITTED WITH SHEETS ATTACHED TO |
| EACHOTHER AS NOT TO HAVE SHEETS FALLING |
| OUT OF SETS ETC. PLANS WERE NOT STAPLED |
| TOGETHER WHEN SUBMITTED. THEY ARE NOW |
| STAPLED BY THIS OFFICE AS NOT TO LOSE |
| ANY SHEETS. ETC. |
| THIS WILL HELP IN THE REVIEW PROCESS. |
| |
| 4) NOTE: PLEASE SEE SEC'S HAVE NOW BEEN |
| DOWN SIZED TO 3/0'S FOR ONE FIRE PUMP |
| SERVICE. |
| PLEASE SEE THAT THE SEC'S SHALL ME SIZED |
| ACCORDINGLY TO THE OCP, HP, AND THE SIZE |
| OF THE FPC. |
| PLEASE SEE 310.16, AS 3/0'S ARE ONLY |
| RATED AT 200A'S AND THE 4/0'S ARE ONLY |
| RATED FOR 225A'S. PLEASE SEE |
| 240.4,310.16. |
| THE OCP SHOWN ON MAIN IS 250A'S. |
| (LOOCKED ROTOR SHOULD BE SET AND PART OF |
| THE FPC AND MUST BE 6X THE FLA'S. |
| 695.4/695.5 |
| |
| THIS RISER SHALL BE REVISED EVEN THOUGH |
| THE RISER WAS SUBMITTEDONLY FOR PANEL |
| "G-1". |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |