Plan Review Notes
Plan Review Notes For Permit 05081014
Permit Number 05081014
Review Stop E
Sequence Number 2
Notes
Date Text
2006-06-10 00:00:00***** UNSAT2ND REVIEW ******
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES DUE TO THE
 PLANS ETC SUBMITTED.
  
 1)NOTE:NOTE #1 NO, PLEASE SEE THIS
 NOTE STILL APPLIES. PLEASE SEE A NEW
 SHEET WAS ADDED FOR THE BUILDING AND
 UNIT LAYOUTS WHICH CONTAIN COMMENTS
 UNDER OTHER REVISIONS WHICH WERE
 SUBMITTED.
 PLEASE SEE THE REVISED RISER WHICH WAS
 SUBMITTED TO ADDRESS THE PANEL "G-1" IN
 QUESTION HAS COMMENTS AS IT WAS REVISED
 FOR OTHER ITEMS. SEE NEW NOTES BELOW.
  
 ** PREVIOUS REVIEW **
 PLEASE SEE PLANS SUBMITTED SEEM
 TO CONTAIN SHEETS FROM REVIEW FOR BLDG
 PERMITTED SETS.
 PLEASE CLARIFY PLANS FOR "SITE" SHOULD
 CONTAIN SHEETS PERTAINING TO SITE ONLY.
 SEE RISER DIAGRAM SUBMITTED DOES NOT
 INCLUDE PANEL "G1". G-1 PANEL SCHEDULE
 SUBMITTED.
  
 2)NOTE: NOTE #2 NO. THESE WERE NOT
 SUBMITTED.
  
 ** PREVIOUS NOTE **
 PLEASE SUBMIT ALL MANUFACTURE
 SPEC/CUT SHEETS FOR GATE MOTORS AND
 CONTROLLER. PLEASE SEE ANY FIRE REVIEW
 COMMENTS FOR "FAIL SAFE" OPERATION IN
 THE EVENT OF POWER FAILURE.
 NOTE WAS SHOWN ON "A" SHEET WHICH
 MENTIONED GATE CAN BE MANUAL.
  
 NEW NOTES
 **************************
  
 3) NOTE: PLEASE KNOW, ALL OLD/VOIDED
 SHEETS SHALL BE COMPLETELY REMOVED FROM
 SETS AND ONLY NEW REVISED SHEET SHOULD
 BE INSERTED INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 PLEASE KNOW, ONLY ONE COPY OF ANY
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 ACCOMPANYING THE THREE NEW COMPLETED
 SETS.
 ** PLEASE BE SURE THESE SETS ARE
 SUBMITTED WITH SHEETS ATTACHED TO
 EACHOTHER AS NOT TO HAVE SHEETS FALLING
 OUT OF SETS ETC. PLANS WERE NOT STAPLED
 TOGETHER WHEN SUBMITTED. THEY ARE NOW
 STAPLED BY THIS OFFICE AS NOT TO LOSE
 ANY SHEETS. ETC.
 THIS WILL HELP IN THE REVIEW PROCESS.
  
 4) NOTE: PLEASE SEE SEC'S HAVE NOW BEEN
 DOWN SIZED TO 3/0'S FOR ONE FIRE PUMP
 SERVICE.
 PLEASE SEE THAT THE SEC'S SHALL ME SIZED
 ACCORDINGLY TO THE OCP, HP, AND THE SIZE
 OF THE FPC.
 PLEASE SEE 310.16, AS 3/0'S ARE ONLY
 RATED AT 200A'S AND THE 4/0'S ARE ONLY
 RATED FOR 225A'S. PLEASE SEE
 240.4,310.16.
 THE OCP SHOWN ON MAIN IS 250A'S.
 (LOOCKED ROTOR SHOULD BE SET AND PART OF
 THE FPC AND MUST BE 6X THE FLA'S.
 695.4/695.5
  
 THIS RISER SHALL BE REVISED EVEN THOUGH
 THE RISER WAS SUBMITTEDONLY FOR PANEL
 "G-1".
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-06-09 00:00:00IN ELEC FOR REVIEW