2005-11-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT A001 INDEX SHEET. ALL SHEETS ON
 INDEX SHEET NOT SUBMITTED. PLEASE SUBMIT
 ALL SHEETS. PLANS NOT COMPLETE. SECTION
 104.2.1.
 2. SHTS I-1 & I-2 INFORMATION REQUIRED
 ON IMPRESSION SEAL OF LANDSCAPE
 ARCHITECT IS NOT IMPRESSED ON THE PLANS.
 PLEASE RESEAL SHEETS. FAC 61G1-16.002(1)
 AND FS 481.321
 3. SHT A101 URINAL REQUIRED IN THE MENS
 TOILET ROOM FOR THE SWIMMING POOL PER
 TABLE 424.1.6.1.
 4. SHT A101 TOILET ROOMS SHALL COMPLY
 WITH SECTIONS 11-4.16, 11-4.18, 11-4.19,
 AND 11-4.22 AND ALL SUBSECTIONS. PLEASE
 PROVIDE A DETAIL SHOWING ALL
 REQUIREMENTS.
 5. SHT A102 TOILET ROOM FOR GUARD HOUSE
 TO COMPLY WITH SECTIONS 11-4.16,
 11-4.19, AND 11-4.22 WITH ALL
 SUBSECTIONS. PLEASE PROVIDE A DETAIL
 SHOWING ALL REQUIREMENTS.
 6. SUBMIT A SANITARY & A WATER RISER
 DIAGRAM FOR THE GUARD HOUSE. SHOW ALL
 PIPE SIZES, TRAPS, VENTS ECT. FOR THE
 SANT. SHOW ALL PIPE SIZES, VALVES, AND,
 IF REQUIRED, WATER HAMMER ARRESTORS PER
 SECTION 604.9.
 7. PLUMBING PLANS FOR SWIMMING POOL
 TOILET ROOMS WERE NOT SUBMITTED. PLEASE
 SUBMIT THE PLUMBING PLANS ALONG WITH THE
 SANT. AND WATER RISER DIAGRAMS. SECTIONS
 104.2.1 & 104.3.1.1.
  