2005-09-19 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- SITE SPECIFIC LAYOUT NEED TO BE
 SIGNED AND SEALED BY THE ENGINEER OF
 RECORD. SEE NOTE #12 OF GENERAL NOTES
 SHEET 1 OF 2 OF MASTER PLAN. INCLUDE
 ENGINEER'S TITLE BLOCK INFORMATION AS
 REQUIRED BY CHAPTER 471 FLORIDA
 STATUTES.
  
 3- CONCRETE DECK ANCHORING DETAIL IN
 DRAWING 1 OF 2 AND PORCH DETAIL IN
 COLUMNS AND BEAMS DRAWING DON'T MATCH.
 ONE DETAIL SAYS 1 3/4" TAPCON EMBEDMENT
 AND THE OTHER SAYS 1 1/2" TAPCON
 EMBEDMENT. REVISE AS REQUIRED.
  
 4- A) ENGINEER'S INFORMATION IN TITLE
 BLOCK IN DRAWING 1 OF 2 IS NOT LEGIBLE.
 PROVIDE LEGIBLE INFORMATION. CHAPTER 471
 FLORIDA STATUTES.
  
 B) ENGINEER'S TILE BLOCK INFORMATION IS
 MISSING ON BEAM AND COLUMN DRAWING.
 PROVIDE INFORMATION AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.