Plan Review Notes For Permit 05080650 |
Permit Number |
05080650 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-08-23 00:00:00 | | | PLEASE NOTE THIS PERMIT CANNOT BE ISSUED | | UNTILL THE GEN. RES PERMIT IS ISSUED.IF | | ALL APPLICACIONS WERE SUBMITTED TOGETHER | | THE PROCESS WOULD BE EXPEDITED. | | | | PROVIDE THE GENERATOR AND TRANSFER | | SWITCH MANUFACTURERS SPEC'S(2 COPIES). | | | | SUBMIT A SITE PLAN INDICATING THE | | LOCATION OF ALL SERVICE AND GENERATOR | | EQUIPMENT SO THAT COMPLIANCE WITH 225.31 | | THROUGH 225.37 CAN BE DETERMINED. | | | | PLEASE PROVIDE CALCULATIONS FOR THE LOAD | | TO BE SERVED BY THE GENERATOR. SEE 700.5 | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|