Plan Review Notes
Plan Review Notes For Permit 05080595
Permit Number 05080595
Review Stop B
Sequence Number 1
Notes
Date Text
2005-09-14 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- IMPACT FEES PAID RECEIPT SUBMITTED
 PR#05040709 DOESN'T MATCH PR# STAMPED ON
 PLANS. REVISE AS REQUIRED.
  
 3- ENERGY CALCS ARE GETTING THE CEILING
 FAN CREDIT. THEREFORE, NEED TO SPECIFY
 CEILING FAN SIZES IN THE ELECTRICAL
 PLAN, INCLUDING FANS REQUIRED IN THE
 GREAT ROOM. SEE TABLE 6-6 CHAPTER 13 FBC
  
 4- ROOF FRAMING PLAN NEEDS TO BE REVISED
 AT ENTRY PORCH AREA. CONCRETE BM DOESN'T
 EXTEND ALL THE WAY BACK TO THE FOYER.
 ALSO, REVISE THE KNEEWALL AT THE LEFT
 HAND SIDE OF THE ROOF. IT'S NOT CONCRETE
 BEAM. SEE PLANS AND REVISE FRAMING PLAN
 AS REQUIRED AND SPECIFY CORRESPONDING
 CONNECTOR. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 5- TRUSS ANCHOR SCHEDULE: REVISE NUMBER
 OF NAILS FOR HUS26. SEE 2005 CATALOGUE.
  
 6- PROVIDE PRODUCT APPROVAL FOR:
 A)INSWING 1HR FIRE RATED DOOR AS SHOWN
 AT ATRIUM.PRODUCT APPROVAL SUBMITTED IS
 FOR "OUTSWING" APPLICATION.
  
 B) WINDOW MULLION SPECIED @ GREAT RM
 FIXED WINDOWS.
  
 C) 12'-0" SLIDING GLASS DOORS.
  
 7- SPECIFY MULLION SIZE AND ANCHORS FOR
 FIXED WINDOWS AT GREAT ROOM. . SIZE
 SPECIFIED ON WINDOW SCHEDULE DOESN'T
 MEET THE CALCULATED DESIGN PRESSURES.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.